Iň täze köpugurly elektronika çözüwleri bilen öýüňizi özgertmegiňiz mümkin — akylly yşyklandyryşdan başlap, ses arkaly dolandyrylýan enjamlara çenli; bularyň hemmesi durmuşy has aňsat, has howpsuz we has baglanyşykly etmek üçin döredilen. Amallaryňyzy Bently Nevada 3500 Gözegçilik ulgamy bilen optimizirlaň, ol näsazlyklaryň öňüni almak we işleme döwrüni iň ýokary derejede saklamak üçin hakyky wagt režiminde wibrasiýa we enjamyň ýagdaýyna gözegçilik edýär.
Haryt kody:V18345-1004210001
Positioner V18345-1004210001 ABB | 4-20mA
Manufacturer: ABB
Product No.: V18345-1004210001
Product Type: Valve Positioner Module
Product Origin: Sweden
Payment:T/T, Western Union
Weight: 1700g
Shipping port: Xiamen
Warranty: 12 months
Paýlaş
- Çalt eltip berme
- 24/7 goldaw
- Hil üpjünçiligi
Düşündiriş
Product Overview
The V18345-1004210001 is an electro-pneumatic positioner from ABB, designed for precise valve control on linear and rotary actuators. Features 4–20 mA two-wire input, HART FSK communication, ATEX EEx nA II T6 protection, and fail-freeze output. Aluminum IP65/NEMA 4X housing. Weight: 1.7 kg. Certified for SIL2 safety loops.
Technical Specifications
| Parameter | Specification |
|---|---|
| Part Number | V18345-1004210001 |
| Manufacturer | ABB |
| Type | Electro-Pneumatic Positioner (TZIDC) |
| Input Signal | 4–20 mA two-wire, max 25 mA / 30 V |
| Min Input Current | 3.4 mA (without feedback), start from 3.8 mA |
| Communication | HART 5.1, FSK module, LKS local connector |
| Explosion Protection | ATEX EEx nA II T6 (Zone 2) |
| Output / Safe Position | Fail freeze (single or double acting) |
| Output Range | 0–6 bar (0–90 psi) |
| Supply Pressure | 1.4–6 bar (20–90 psi) |
| Air Consumption | <0.03 kg/h / 0.015 scfm |
| Air Capacity (1.4 bar) | 5.0 kg/h = 3.9 Nm³/h = 2.3 scfm |
| Air Capacity (6 bar) | 13 kg/h = 10 Nm³/h = 6.0 scfm |
| Air Quality | DIN/ISO 8573-1 Class 3 (5 µm, 5 mg/m³, oil 1 mg/m³) |
| Housing Material | Aluminum, varnished, RAL 9005 |
| Protection Class | IP65 / NEMA 4X |
| Pneumatic Connections | G 1/4 or 1/4-18 NPT |
| Electrical Connections | 2 threads 1/2-14 NPT or M20x1.5 |
| Screw Terminals | Max 1.0 mm² (options) / 2.5 mm² (analog signal) |
| Digital Input | 24 V DC (12–30 V DC), max 4 mA |
| Digital Output | 5–11 V DC (NAMUR DIN 19234) |
| Load Voltage (20 mA) | 8.7 V DC (non-Ex) / 9.7 V DC (intrinsically safe) |
| Impedance (20 mA) | 435 Ω (non-Ex) / 485 Ω (intrinsically safe) |
| Angle of Rotation | 25–120° (rotary, optional 270°); 25–60° (linear) |
| Travel Limit | 0–100%, min range >20% |
| Travel Time Prolongation | 0–200 seconds per direction |
| Characteristic Deviation | ≤0.5% |
| Tolerance Band | 0.3–10% adjustable |
| Dead Band | 0.1–10% adjustable |
| Resolution | >4000 steps |
| Sample Rate | 20 ms |
| Temperature Influence | ≤0.5% per 10°C |
| Vibration Influence | ≤±1% up to 10 g and 80 Hz |
| Seismic Compliance | DIN/IEC 68-3-3 Class III |
| Ambient Temperature | -40°C to +85°C |
| Humidity (Operational) | 95% annual average, condensation permissible |
| Humidity (Transport/Storage) | 75% annual average, non-condensing |
| Safety | SIL2 safety loops |
| Approvals | ATEX, FM, CSA, IECEx |
| Weight | 1.7 kg |
Installation & Maintenance
Mounting
Mount to linear actuators per DIN/IEC 534/NAMUR or rotary actuators per VDI/VDE 3845. Integral mounting ready. Mechanical position indicator provides visual feedback. Mounting orientation has no effect on performance.
Air Supply
Use instrument air free of oil, water, and dust per DIN/ISO 8573-1 Class 3: max particle 5 µm, density 5 mg/m³, oil 1 mg/m³, dew point 10 K below operating temperature. Do not exceed actuator max operating pressure.
Hazardous Area Installation
ATEX EEx nA II T6 (Zone 2) approved. Ambient temperature limits: T4 -40°C to +85°C, T5 -40°C to +65°C, T6 -40°C to +50°C. Also certified for FM/CSA intrinsically safe and IECEx Ex ib IIC T6 applications.
Engineering Advantages
Fail-Freeze Safety
On electrical power failure, the actuator blocks in its last position (fail freeze). Ensures process continuity and safe operation in critical applications. Certified for SIL2 safety loops.
ATEX Zone 2 Protection
ATEX EEx nA II T6 certification enables installation in Zone 2 hazardous areas. Also certified for FM/CSA intrinsically safe and IECEx Ex ib IIC T6 applications.
Precise Valve Control
Resolution >4000 steps with 20 ms sample rate. Characteristic deviation ≤0.5%. Freely configurable characteristic curves with 20 reference points. HART FSK communication for remote diagnostics.
Technical FAQs
Q1: What is the fail-safe behavior on electrical power failure?
A1: Fail freeze. The actuator blocks in its last position on loss of electrical power. Air is vented from the actuator or the actuator is blocked.
Q2: What explosion protection does this model provide?
A2: ATEX EEx nA II T6 (Zone 2). Also certified for FM/CSA intrinsically safe and IECEx Ex ib IIC T6.
Q3: What communication protocol does this positioner use?
A3: HART 5.1 via FSK module over the 20 mA signal line. Also supports LKS local communication interface.
Goşmaça spesifikasiýalar
- Kümüş
Skalyar (V/f)
Wektor
AC tok bilen işleýän
Satyn alyş gollanmasy
- Sargyt etmezden ozal takyk modeli, bölek belgisini we aýratynlyklary tassyklaň.
- Bar bolan enjamyňyz ýa-da dolandyryş ulgamlaryňyz bilen laýyklygyny üpjün ediň.
- Tehniki kömek üçin sale@etowonauto.com ýa-da +8617859788089 arkaly habarlaşyň.
- Eltip beriş mümkinçiliklerini, öňdebaryş möhletlerini we iberiş talaplaryny gözden geçiriň.
- Gurnama wagty öndürijiniň görkezmelerine hem-de iň oňat tejribelere eýeriň.
Eltip bermek we gaýtarmak
Stokda bar bolan harytlar adatça şol bir iş gününde ugradylýar. Häzir stokda bolmadyk önümler üçin iberiş wagty elýeterliligine görä üýtgäp biler. Halkara eltip bermek mümkindir we eltip bermek tölegleri barýan ýeriňe, agramyna we daşaýjynyň saýlanmagyna görä hasaplanýar.
Harytlar ulanylman we asyl ýagdaýynda bolmak şerti bilen, alnan gününden başlap 30 günüň içinde yzyna gaýtarmak kabul edilýär. Yzyna iberiş üçin eltip bermek çykdajylary müşderiniň jogapkärçiliginde. Yzyna gaýtarmak baradaky rugsaty almak üçin, haýsydyr bir harydy yzyna ugratmazdan öň biziň bilen habarlaşmagyňyzy haýyş edýäris.
Has giňişleýin maglumat üçin, biziň Iberiş we yzyna gaýtarmak syýasatymyzy.

3500/61-05-CN Temperature Monitor Module | Bently Nevada
3500/22-01-02-CN TDI Module Bently Nevada
Bently Nevada 3500/42-04-00 | Seismic Monitor
-
Çalt eltip bermek
Asyl senagat awtomatizasiýa şaýlary gyssagly iberiliş üçin bütin dünýä boýunça elýeterlidir.
-
Aňsat gaýtaryşlar
Ygtybarly satuwdan soňky gorag üçin 30 günlük yzyna gaýtarmak goldawy we 12 aýlyk kepilnama.
-
24/7 goldaw
Durnukly we netijeli işleýşi saklamaga ýardam edýän çeýe, professional goldaw.
-
Hakyky we Asyl
100% hakyky, ygtybarly senagat awtomatizasiýasy öndürijilerinden gönüden-göni üpjün edilýär.
Tehniki we satyn alyş gollanmasy
-
How Can You Tune GE RX3i and RX7i Ethernet for Heavy Industry?
Intermittent Ethernet timeouts on GE RX3i and RX7i controllers are among the hardest faults in heavy process plants, ...
-
Why Does FCS Redundancy Not Protect Your HIS Configuration?
This article examines the operational risks of Yokogawa CENTUM VP HIS lockups and explains why FCS controller re...
-
How Does 1756 Analog I/O Calibration Drift Affect PLC Accuracy?
This article examines calibration drift in Allen-Bradley ControlLogix 1756 analog I/O modules, presenting quanti...
-
Why Do 31% of ABB 800xA S800 IO Hot Swaps Fail in DCS Systems?
ABB 800xA S800 hot swap failures rarely stem from defective hardware. Field data from 142 card replacement jobs shows...
-
How Do You Diagnose Degraded MTL Surge Protection Devices?
This article presents field-proven diagnostic checks, aging benchmarks, and installation rules for MTL surge pro...
-
How Can You Stop Nuisance Trips on Bently Nevada TSI Systems?
Nuisance trips on Bently Nevada TSI racks cost power and oil & gas plants $18,000 to $45,000 per event and occur ...