Transform your home with the latest multi-electronics solutions, from intelligent lighting to vOptimize your operations with the Bently Nevada 3500 Monitoring System, offering real-time vibration and machinery condition monitoring to prevent failures and maximize uptime.oice-controlled devices all designed to make life easier, safer, and more connected.
SKU:FS-TSDI-1624C
Honeywell FS-TSDI-1624C 24V Safety Input FTA
Manufacturer: Honeywell
Product No.: FS-TSDI-1624C
Product Type: Input Module
Product Origin: USA
Payment:T/T, Western Union
Weight: 200g
Shipping port: Xiamen
Warranty: 12 months
Share
- Fast Delivery
- 24/7 Support
- Quality Assurance
Description
Product Overview
The FS-TSDI-1624C is a high-reliability Field Termination Assembly (FTA) module designed to interface between field wiring and the Honeywell Safety Manager system. This module provides 16 current-limited digital input channels specifically approved for routing non-incendive field circuits into Class I, Division 2 hazardous locations.
Core Technical Advantages
Class I, Division 2 Hazardous Location Safety
Engineered with precise energy-limiting circuitry, this module restricts igniting current to less than 100 mA per channel under worst-case voltage conditions. This design allows direct interfacing with field devices located in explosive gas atmospheres without the need for additional bulky intrinsic safety barriers.
Dual-Group Fuse Protection
The 16 channels are divided into two isolated groups of 8. Each group features a high-voltage rated 250 mA SOC SHV12 ceramic fuse on the common positive line, preventing field-side short circuits from disabling the entire module and isolating faults effectively.
Redundant Module Compatibility
The hardware architecture natively accepts dual connection paths, allowing a single FTA block to drive a redundant pair of safety input cards simultaneously. This architecture eliminates single points of failure between the field termination and the safety logic layer.
Technical Specifications
| Parameter | Specification Details |
|---|---|
| Manufacturer | Honeywell (Safety Manager) |
| Model Type | FS-TSDI-1624C / FC-TSDI-1624C |
| Channel Configuration | 16 Channels (2 Groups of 8) |
| Nominal Input Voltage | 24 V DC (-15% to +30%) |
| Input Current Load | ≤ 15 mA at 24 V DC (with Redundant Load) |
| Igniting Current Limit | < 100 mA at 24 V DC +30% (per channel) |
| Fuse Rating / Model | 250 mA, 400 V AC/DC (SOC SHV12) |
| Dimensions (L × W × H) | 170 × 70 × 60 mm (6.69 × 2.76 × 2.36 in) |
Class I Division 2 Loop Parameter Limits
To preserve non-incendive loop integrity, interconnected field wiring must comply strictly with the following electrical constraints:
- Max. Closed Loop Resistance: 250 Ω
- Min. Open Loop Resistance: 15 kΩ
- Hydrogen Environments (Group A & B): Max. Inductance = 8 mH | Max. Capacitance = 0.3 μF
- Non-Hydrogen Environments (Group C & D): Max. Inductance = 22 mH | Max. Capacitance = 7 μF
Installation and Maintenance
DIN Rail Mounting
Snap the module securely onto standard TS32 or TS35 DIN EN rails. The physical installation requires an absolute minimum rail length of 171 mm to guarantee stability and adequate side spacing inside the enclosure panel.
Field Connection Protocols
Connect field wires using copper conductors up to a maximum size of 2.5 mm² (AWG 14). Strip the wire insulation back exactly 7 mm (0.28 in). Secure the wire inside the terminal block by applying a precise tightening torque of 0.5 Nm (0.37 ft-lb) to avoid damage to the terminal frame.
Fuse Replacement Standards
If a group experiences a dead short circuit, verify loop integrity before replacing the fuse. Only use original manufacturer part numbers (SOC SHV12 250 mA) to maintain the certified non-incendive thermal thresholds. Note that the maximum sustained output current per fuse must not exceed 175 mA.
Engineering Advantages
Compact Footprint Optimization
Measuring just 170 mm in length, this module optimizes internal cabinet space compared to traditional terminal blocks combined with external fuse holders, providing high-density I/O allocation.
Reduced Total Cost of Ownership
By achieving Class I, Division 2 approval directly through internal current-limiting design, the assembly removes the requirement for expensive intrinsically safe galvanic isolators and dedicated grounding systems.
Global Safety Certifications
The module holds full industrial compliance stamps including CE, TÜV, UL, CSA, and FM, meeting the rigorous standards necessary for deployment in global refining, petrochemical, and chemical complexes.
Technical FAQs
Q1: Why is the maximum output current per fuse limited to 175 mA when the fuse itself is rated for 250 mA?
A1: The 175 mA limit enforces a safe engineering safety margin. This constraint prevents continuous operation near the thermal trip point of the fuse, preventing nuisance blowing caused by minor ambient temperature fluctuations or temporary current ripples.
Q2: What happens to the remaining 7 channels if one channel develops a short circuit to ground?
A2: If a short circuit draws current exceeding the fuse threshold on a single channel, the 250 mA common fuse for that specific group of 8 will open. This protects the system backplane but drops power to all 8 channels within that isolated group. The opposite group of 8 will continue running normally.
Q3: Can this module be used with non-certified standard digital input devices in hazardous areas?
A3: Yes, provided that the overall field circuit matches the non-incendive loop parameters (maximum loop resistance, inductance, and capacitance) defined for Gas Groups A-D. The current-limiting features of the FTA ensure that field wiring faults cannot generate a spark with sufficient thermal energy to ignite the atmosphere.
Additional Specifications
- Orange
Scalar (V/f)
Vector
AC-powered
Buying Guide
- Confirm the exact model, part number, and specifications before ordering.
- Ensure compatibility with your current machinery or control systems.
- Reach out via sale@etowonauto.com or +8617859788089 for technical assistance.
- Review delivery options, lead times, and shipping requirements.
- Follow manufacturer instructions and best practices during installation.
Shipping And Return
In-stock items are typically dispatched the same business day. For products not currently in stock, dispatch times may vary based on availability. International shipping is available, and shipping costs are calculated according to destination, weight, and carrier selection.
Returns are accepted within 30 days of receipt, provided items are unused and in original condition. Return shipping costs are the responsibility of the customer. Please contact us before returning any item to receive return authorization.
For more details, please review our Shipping & Return Policy.

3500/61-05-CN Temperature Monitor Module | Bently Nevada
3500/22-01-02-CN TDI Module Bently Nevada
Bently Nevada 3500/42-04-00 | Seismic Monitor
-
Fast Shipping
Original industrial automation parts available for prompt shipment worldwide.
-
Easy Returns
30-day return support with a 12-month warranty for reliable after-sales protection.
-
24/7 support
Responsive professional support to help maintain stable and efficient operations.
-
Genuine & Original
100% authentic, sourced directly from trusted industrial automation manufacturers.
Technical & Buying Guide
-
Can DCS Intelligent Regulation Fix Thermal Power Energy Imbalance?
This article explains how intelligent DCS regulation with MPC and cloud-based control solves energy-production imbala...
-
Can Continuous Automation Iteration Cut Factory Costs by 18-25%?
Static industrial control systems create hidden annual cost increases of 18-25%. Phased PLC and DCS program iteration...
-
Can Anti-Interference Hardware End 38% of Automation Downtime?
Field data from chemical, wind, and automotive plants proves that industrial hardware with full IEC 61000-4 EMC certi...
-
How Does Full-Lifecycle Management Optimize PLC and DCS Assets?
Traditional industrial asset management relies on manual logging and reactive troubleshooting, causing 15–20% annual ...
-
Can an Integrated Spare Chain Slash Downtime?
Unplanned equipment failures cost Chinese factories ¥636,000 per hour. Traditional cross-border spare procurement tak...
-
Why Do 30% of Automation Upgrades Fail Due to Integration Gaps?
This technical article explains how digital-intelligent fusion overcomes fragmented workshop operations using industr...
