Skip to content
Automation parts, worldwide supply
Skip to product information
1 of 3

SKU:6ES7422-1BH11-0AA0

Siemens 6ES7422-1BH11-0AA0 S7-400 SM 422 16 DO 2A

In stock (13 units), ready to be shipped
  • Manufacturer: Siemens

  • Product No.: 6ES7422-1BH11-0AA0

  • Product Type: Digital Output Module

  • Product Origin: DE

  • Payment:T/T, Western Union

  • Weight: 600g

  • Shipping port: Xiamen

  • Warranty: 12 months

30-Day Return Policy · 12-Month Warranty
  • Fast Delivery
  • 24/7 Support
  • Quality Assurance

Description

Siemens 6ES7422-1BH11-0AA0 SIMATIC S7-400 SM 422 Digital Output Module

Siemens 6ES7422-1BH11-0AA0 is a SIMATIC S7-400 SM 422 digital output module with 16 isolated 24V DC outputs rated at 2A. Features clocked electronic short-circuit protection and 500V DC isolation. Weight approximately 600 g.

Key Specifications

Parameter Value
Article No. 6ES7422-1BH11-0AA0
Product Type Digital Output Module SM 422
Number of Outputs 16
Output Voltage 24V DC (20.4-28.8V)
Rated Output Current 2A per channel
Backplane Current (5V) 160 mA max
Load Current (L+ without load) 30 mA max
Power Loss 5W typical
Weight Approximately 600 g

Output Specifications

Parameter Value
Output Current Range 5 mA min to 2.4A max
Residual Current (Signal "0") 0.5 mA max
Output Voltage (Signal "1") L+ (-0.5V) minimum
Load Resistance Range 24 Ω to 4 kΩ
Output Delay 1 ms max (0 to 1 and 1 to 0)
Lamp Load Switching 10W max
Short-Circuit Protection Clocked electronically (2.8-6A threshold)

Switching Frequency

Load Type Max Frequency
Resistive 100 Hz
Inductive 0.1 Hz
Inductive (IEC 60947-5-1, DC13) 0.2 Hz at 1A / 0.1 Hz at 2A
Lamp Load 10 Hz

Isolation & Environmental

Parameter Value
Channel Separation Yes, in groups of 8
Channels to Backplane Yes
Isolation Test Voltage 500V DC
Total Current per Group 3A up to 40°C / 2A up to 60°C
Cable Length (Shielded) 1000 m max
Cable Length (Unshielded) 600 m max

Dimensions

Parameter Value
Width 25 mm
Height 290 mm
Depth 210 mm

FAQs

Q1: What is the rated output current?
A1: 2A per channel with a permissible range of 5 mA to 2.4A.

Q2: Can two outputs be paralleled for higher current?
A2: No, not possible for uprating. Redundant control is possible only within the same group.

Q3: What is the isolation test voltage?
A3: 500V DC with channel separation in groups of 8.

Product Resources

📄 Download PDF

Scalar (V/f)

Vector

AC-powered

  • Confirm the exact model, part number, and specifications before ordering.
  • Ensure compatibility with your current machinery or control systems.
  • Reach out via sale@etowonauto.com or +8617859788089 for technical assistance.
  • Review delivery options, lead times, and shipping requirements.
  • Follow manufacturer instructions and best practices during installation.

In-stock items are typically dispatched the same business day. For products not currently in stock, dispatch times may vary based on availability. International shipping is available, and shipping costs are calculated according to destination, weight, and carrier selection.

Returns are accepted within 30 days of receipt, provided items are unused and in original condition. Return shipping costs are the responsibility of the customer. Please contact us before returning any item to receive return authorization.

For more details, please review our Shipping & Return Policy.

View Product Details

ENSURE RELIABLE MACHINERY PERFORMANCE

Transform your home with the latest multi-electronics solutions, from intelligent lighting to vOptimize your operations with the Bently Nevada 3500 Monitoring System, offering real-time vibration and machinery condition monitoring to prevent failures and maximize uptime.oice-controlled devices all designed to make life easier, safer, and more connected.