Skip to content
Automation parts, worldwide supply
Skip to product information
1 of 3

SKU:330103-09-13-10-02-00

Bently Nevada 330103-09-13-10-02-00 Probe | Original

In stock (20 units), ready to be shipped
  • Manufacturer: Bently Nevada

  • Product No.: 330103-09-13-10-02-00

  • Product Type: Proximity Probe

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 323g

  • Shipping port: Xiamen

  • Warranty: 12 months

30-Day Return Policy · 12-Month Warranty
  • Fast Delivery
  • 24/7 Support
  • Quality Assurance

Description

Bently Nevada 330103-09-13-10-02-00 Proximity Probe

The 330103-09-13-10-02-00 (also cataloged as the 330103 3300 XL 8 mm Proximity Probe, Metric) provides radial vibration and axial position measurement in 3300 XL machinery monitoring systems. It has a PPS probe tip, an AISI 303/304 stainless steel case, an M10x1 thread, and a Miniature coaxial ClickLoc connector with 1.0 m cable. Probe cable weight is 323 g/m.

Hardware Specifications

Parameter Specification
Model 330103-09-13-10-02-00
Brand Bently Nevada
Product Type 3300 XL 8 mm Proximity Probe, Metric
Unthreaded Length 90 mm
Overall Case Length 130 mm
Total Length 1.0 m (3.3 ft)
Connector Miniature coaxial ClickLoc, standard cable
Probe Tip Material Polyphenylene sulfide (PPS)
Case Material AISI 303 or 304 stainless steel
Case Thread M10x1, max. thread engagement 15 mm
Nominal Probe DC Resistance 7.59 +/- 0.50 ohms at 1.0 m
Linear Range 0.25 to 2.3 mm (10 to 90 mils), approx. -1 to -17 Vdc
Recommended Gap Setting -9 Vdc [approx. 1.27 mm (50 mils)]
Operating Temp (Standard Probe) -52 deg C to +177 deg C
Field Wiring 0.2 to 1.5 mm2 (16 to 24 AWG), 3 conductor shielded triad, max. 305 m
Probe Weight 323 g/m (11.4 oz/m)

Gap Voltage and Signal Characteristics

The 330103 probe operates over a 2 mm (80 mils) linear range beginning at approximately 0.25 mm (10 mils) from the target and extending to 2.3 mm (90 mils), corresponding to approximately -1 to -17 Vdc. The recommended gap setting for radial vibration measurement is -9 Vdc, approximately 1.27 mm (50 mils). Nominal DC resistance from center conductor to outer conductor is 7.59 +/- 0.50 ohms for the 1.0 m probe length. The probe seals differential pressure between tip and case with a Viton O-ring; probes are not pressure tested prior to shipment. Average Scale Factor changes less than 3 % when tested in 93 % humidity per IEC 68-2-3 for up to 56 days. Field wiring uses 3 conductor shielded triad cable, tinned, from 0.2 to 1.5 mm2 (16 to 24 AWG), with a maximum length of 305 m (1000 ft) between the Proximitor Sensor and the monitor; signal roll-off at high frequencies occurs with longer field wiring. Standard probe temperature range is -52 deg C to +177 deg C. Exposure below -34 deg C may cause premature failure of the pressure seal. With intrinsically safe zener barriers per drawing 141092 or galvanic isolators, the probe meets Class I, Zone 0 AEx/Ex ia IIC T5...T1 Ga and Class I, Groups A-D, Class II, Groups E-G, Class III. With a nonincendive circuit per drawing 140979, it meets Class I, Zone 2 AEx/Ex nA IIC T5...T1 Gc, Class I Division 2 Groups A-D, and Class I Zone 2 AEx/Ex ec IIC T5...T1 Gc.

Field Installation Guidelines

Mount the probe in an M10x1 threaded hole with a maximum thread engagement of 15 mm. Confirm the unthreaded length of 90 mm and overall case length of 130 mm clear the machine housing and bracket. Set the radial vibration gap to -9 Vdc (approximately 1.27 mm or 50 mils) using a calibrated voltmeter before locking the probe. Route the 1.0 m ClickLoc cable and field extension through 3 conductor shielded triad cable, terminated with tinned conductors, with a total length not exceeding 305 m to the Proximitor Sensor. Ground the shield at the monitor end only. For hazardous area installation, verify the barrier or isolator matches drawing 141092 (ia) or drawing 140979 (nA) and confirm the area classification against the certification marking. Do not expose the probe to temperatures below -34 deg C to protect the pressure seal.

Frequently Asked Questions

Q: What is the recommended gap setting for radial vibration on the 330103-09-13-10-02-00?
A: -9 Vdc, approximately 1.27 mm (50 mils).

Q: What is the nominal probe DC resistance at 1.0 m?
A: 7.59 +/- 0.50 ohms from center conductor to outer conductor.

Q: What is the maximum field wiring length between the Proximitor Sensor and the monitor?
A: 305 m (1000 ft) using 3 conductor shielded triad cable.

Scalar (V/f)

Vector

AC-powered

  • Confirm the exact model, part number, and specifications before ordering.
  • Ensure compatibility with your current machinery or control systems.
  • Reach out via sale@etowonauto.com or +8617859788089 for technical assistance.
  • Review delivery options, lead times, and shipping requirements.
  • Follow manufacturer instructions and best practices during installation.

In-stock items are typically dispatched the same business day. For products not currently in stock, dispatch times may vary based on availability. International shipping is available, and shipping costs are calculated according to destination, weight, and carrier selection.

Returns are accepted within 30 days of receipt, provided items are unused and in original condition. Return shipping costs are the responsibility of the customer. Please contact us before returning any item to receive return authorization.

For more details, please review our Shipping & Return Policy.

View Product Details

ENSURE RELIABLE MACHINERY PERFORMANCE

Transform your home with the latest multi-electronics solutions, from intelligent lighting to vOptimize your operations with the Bently Nevada 3500 Monitoring System, offering real-time vibration and machinery condition monitoring to prevent failures and maximize uptime.oice-controlled devices all designed to make life easier, safer, and more connected.