Beschrijving

MTL5012 Solid-State Output Interface

The MTL5012 from MTL Instruments enables solid-state outputs in safe areas to be controlled by switches or proximity detectors in hazardous areas. This single-channel interface provides independent output phase reversal and comprehensive line fault detection. It delivers reliable performance for logic circuit applications in demanding industrial environments.

Key Technical Specifications

  • Brand: MTL Instruments
  • Model: MTL5012
  • Product Type: Solid-State Output Interface
  • Channels: One channel
  • Output Type: Floating solid-state for logic circuits
  • Frequency Range: DC to 5kHz
  • Input Standard: NAMUR/DIN 19234

Hazardous Area Certification

  • Switch Location: Zone 0, IIC, T6 hazardous area
  • Detector Location: Zone 0, IIC, T4-T6 with certification
  • Division Rating: Division 1, Group A hazardous location
  • The MTL5012 maintains intrinsic safety for connected sensors

Input Specifications

  • Sensor Voltage: 7 to 9V from 1kΩ ±10% source
  • Normal Phase: Output on if Iin >2.1mA or Rin <2kΩ
  • Reverse Phase: Output off under same conditions
  • Hysteresis: 200µA typical for stable switching
  • Phase Reversal: User-selectable for output configuration

Output Characteristics

  • Operating Frequency: DC to 5kHz
  • Maximum Off-state Voltage: 35V
  • Off-state Leakage: 10µA maximum
  • On-state Voltage Drop: 1 + (0.13 x current in mA) V
  • Maximum On-state Current: 50mA
  • Compatibility: Floating output for logic circuits

Line Fault Detection (LFD)

  • LFD Mode: User-selectable operation
  • Open-circuit Alarm: On if Iin <50µA, Off if Iin >150µA
  • Short-circuit Alarm: On if Rin <100Ω, Off if Rin >360Ω
  • Fault Response: Detected line fault switches off output
  • Contact Input: Requires 500Ω-1kΩ series and 20kΩ-25kΩ parallel resistors

Terminal Configuration

  • Input: Terminal 1 (Input –ve), Terminal 2 (Input +ve)
  • Earth Leakage: Terminal 3 for detection
  • Output: Terminal 10-11 (Output –ve), Terminal 12 (Output +ve)
  • Power Supply: Terminal 13 (Supply –ve), Terminal 14 (Supply +ve)

Power Requirements

  • Current Consumption: 30mA at 24V maximum
  • Power Dissipation: 0.8W at 24V maximum
  • Maximum Dissipation: 1.2W at 35V
  • Isolation: 250V AC or DC between all circuits

Safety Parameters

  • Safety Voltage: 10.5V maximum
  • Internal Resistance: 800Ω
  • Safety Current: 14mA maximum
  • Maximum Voltage: Um = 250V rms or DC

Frequently Asked Questions

  • What type of output does the MTL5012 provide?
    It provides a floating solid-state output compatible with logic circuits.
  • How does line fault detection work?
    It detects open circuits (<50µA) and short circuits (<100Ω) with visual indication.
  • What is the maximum operating frequency?
    It operates from DC to 5kHz for high-speed applications.
  • Can I reverse the output logic?
    Yes, it features user-selectable phase reversal for output configuration.

For pricing and technical support, please contact sale@etowonauto.com

🏷️ Tags: Detector Interface

Scalar (V/f)

Vector

Op netstroom

  • Bevestig het exacte model, onderdeelnummer en specificaties voordat u bestelt.
  • Zorg voor compatibiliteit met uw huidige machines of besturingssystemen.
  • Neem contact op via sale@etowonauto.com of +8617859788089 voor technische ondersteuning.
  • Bekijk de leveringsopties, doorlooptijden en verzendvereisten.
  • Volg de instructies van de fabrikant en de beste praktijken tijdens de installatie.

Voorraadartikelen worden doorgaans dezelfde werkdag verzonden. Voor producten die momenteel niet op voorraad zijn, kunnen de verzendtijden variëren afhankelijk van de beschikbaarheid. Internationale verzending is mogelijk, en de verzendkosten worden berekend op basis van bestemming, gewicht en gekozen vervoerder.

Retourzendingen worden geaccepteerd binnen 30 dagen na ontvangst, mits de artikelen ongebruikt en in originele staat zijn. De kosten voor retourzending zijn voor rekening van de klant. Neem alstublieft contact met ons op voordat u een artikel retourneert om een retourautorisatie te ontvangen.

Voor meer details kunt u onze Verzend- en Retourbeleid raadplegen.

Alle details bekijken

ZORG VOOR BETROUWBARE MACHINEPRESTATIES

Transformeer je huis met de nieuwste multi-elektronica oplossingen, van intelligente verlichting tot spraakgestuurde apparaten, allemaal ontworpen om het leven gemakkelijker, veiliger en meer verbonden te maken.