Forvandle hjemmet ditt med de nyeste multi-elektroniske løsningene, fra intelligent belysning til stemmestyrte enheter – alle designet for å gjøre livet enklere, tryggere og mer tilkoblet. Optimaliser driften med Bently Nevada 3500 overvåkingssystem, som tilbyr sanntids vibrasjons- og maskintilstandsovervåking for å forhindre feil og maksimere oppetid.
SKU:V18345-1010421001
ABB | Electro-Pneumatic Positioner ATEX IECEx V18345-1010421001
Manufacturer: ABB
Product No.: V18345-1010421001
Product Type: Valve Positioner Module
Product Origin: Sweden
Payment:T/T, Western Union
Weight: 1700g
Shipping port: Xiamen
Warranty: 12 months
Del
- Rask levering
- 24/7 kundestøtte
- Kvalitetssikring
Beskrivelse
ABB V18345-1010421001 TZIDC Electro-Pneumatic Positioner
Product Overview
ABB V18345-1010421001 is an intelligent, configurable electro-pneumatic positioner from the TZIDC series with indicator and operator panel. Features varnished aluminum case IP65 (NEMA 4X) for mounting to linear actuators per DIN/IEC 534/NAMUR or rotary actuators per VDI/VDE 3845. Accepts 4-20mA two-wire input with LKS adapter connector plug. Double acting fail safe action. Includes plug-in analog position feedback module 4-20mA. ATEX and IECEx certified for hazardous areas. Weight 1.7 kg.
Model Number Decoder
| Position | Code | Meaning |
|---|---|---|
| Base | V18345 | TZIDC intelligent, configurable with indicator and operator panel |
| Case/Mounting | 1 | Varnished aluminum IP65, DIN/IEC 534/NAMUR or VDI/VDE 3845 |
| Input/Communication | 1 | 4-20mA two-wire with LKS adapter connector |
| Explosion Protection | 0 | Without |
| Output/Safe Position | 4 | Double acting, fail safe |
| Connections | 2 | Cable 1/2-14 NPT, Air 1/4-18 NPT |
| Option Modules | 1 | Plug-in analog position feedback 4-20mA |
| Mech Feedback | 0 | Without |
| Design | 1 | Standard |
Technical Specifications
| Parameter | Value |
|---|---|
| Brand | ABB |
| Model | V18345-1010421001 |
| Type | TZIDC Electro-Pneumatic Positioner |
| Action | Double Acting, Fail Safe |
| Output Signal | 4 to 20 mA two-wire |
| Digital Input | 0 to 5V DC (logic 0), 11 to 30V DC (logic 1) |
| Digital Output | 5 to 11V DC per DIN 19234/NAMUR |
| Supply Pressure | 1.4 to 6 bar (20 to 90 psi) |
| Air Consumption | < 0.03 kg/h (0.015 scfm) |
| Housing Material | Aluminum, epoxy resin varnish |
| Protection Class | IP65, NEMA 4X |
| Electrical Connection | 2 threads 1/2-14 NPT or M20x1.5 |
| Pneumatic Connection | G 1/4 or 1/4-18 NPT |
| ATEX Intrinsically Safe | II 2G EEx ib IIC T6 |
| ATEX Zone 2 | II 3G EEx n A II T6 |
| IECEx | Ex ib IIC T6 |
| Temperature T4 | 40°C to +85°C |
| Temperature T5 | 40°C to +50°C |
| Temperature T6 | 40°C to +35°C |
| Weight | 1.7 kg |
Installation
Mount on linear actuators per DIN/IEC 534/NAMUR or rotary actuators per VDI/VDE 3845. Ready for integral mounting. Connect 4-20mA two-wire input with LKS adapter. Wire electrical connection at 1/2-14 NPT or M20x1.5. Connect air supply at G 1/4 or 1/4-18 NPT with 1.4 to 6 bar pressure. For hazardous areas, observe ATEX temperature class limits: T4 up to 85°C, T5 up to 50°C, T6 up to 35°C. Verify IP65 seal after installation.
Features
Intelligent configurable positioner with indicator and operator panel. Double acting fail safe action for power failure safety. ATEX II 2G EEx ib IIC T6 intrinsically safe certification. ATEX II 3G EEx n A II T6 Zone 2 certification. IECEx Ex ib IIC T6 certified. 4-20mA two-wire input with LKS adapter. Plug-in analog position feedback 4-20mA. Air consumption less than 0.03 kg/h independent of supply pressure. Aluminum case with epoxy resin varnish.
FAQ
Q1: What hazardous area certifications does this positioner have?
A1: ATEX II 2G EEx ib IIC T6 intrinsically safe, ATEX II 3G EEx n A II T6 Zone 2, and IECEx Ex ib IIC T6. Certificate TÜV 98 ATEX 1370 X.
Q2: What is the action type and fail position?
A2: Double acting with fail safe action. In case of electrical power failure, the valve moves to its safe position. 4-20mA two-wire input.
Q3: What are the temperature class limits?
A3: T4 rated 40°C to +85°C. T5 rated 40°C to +50°C. T6 rated 40°C to +35°C. Supply pressure 1.4 to 6 bar.
Ytterligere spesifikasjoner
- Sølv
Skalar (V/f)
Vektor
AC-drevet
Kjøpsveiledning
- Bekreft nøyaktig modell, delenummer og spesifikasjoner før bestilling.
- Sørg for kompatibilitet med ditt nåværende maskineri eller kontrollsystemer.
- Ta kontakt via sale@etowonauto.com eller +8617859788089 for teknisk assistanse.
- Gå gjennom leveringsalternativer, leveringstider og fraktkrav.
- Følg produsentens instruksjoner og beste praksis under installasjon.
Frakt og retur
Varer på lager sendes vanligvis samme virkedag. For produkter som ikke er på lager for øyeblikket, kan leveringstiden variere basert på tilgjengelighet. Internasjonal frakt er tilgjengelig, og fraktkostnader beregnes ut fra destinasjon, vekt og valgt transportør.
Returer godtas innen 30 dager etter mottak, forutsatt at varene er ubrukte og i original stand. Returfraktkostnader dekkes av kunden. Vennligst kontakt oss før du returnerer en vare for å få returautorisasjon.
For mer informasjon, vennligst se vår Frakt- og returpolicy.

3500/61-05-CN Temperature Monitor Module | Bently Nevada
3500/22-01-02-CN TDI Module Bently Nevada
Bently Nevada 3500/42-04-00 | Seismic Monitor
-
Rask levering
Originale deler til industriell automasjon tilgjengelig for rask levering over hele verden.
-
Enkel retur
30 dagers returrett med 12 måneders garanti for pålitelig etterkjøpsbeskyttelse.
-
24/7 støtte
Responsiv profesjonell støtte for å hjelpe med å opprettholde stabile og effektive operasjoner.
-
Ekte og original
100 % autentisk, hentet direkte fra pålitelige produsenter av industriell automasjon.
Teknisk og kjøpsguide
-
How Does the Bently Nevada 3500/42M Vibration Module Drift?
This technical guide examines the Bently Nevada 3500/42M vibration module within industrial automation architect...
-
What Causes IC694MDL Fault Codes in GE RX3i PLC Systems?
This guide explains GE RX3i IC694MDL discrete I/O fault codes, key electrical parameters, ESD and torque requirements...
-
What CFC Rules Cut PCS7 Batch Abort Rates Fast?
This article presents enforceable CFC programming governance rules for Siemens PCS7 DCS batch plants, covering b...
-
What Makes the 1769-L3ER Ideal for Compact Skid Automation?
This guide explains how the Allen-Bradley 1769 CompactLogix L3ER bridges the gap between micro PLCs and large DC...
-
Why Do SIL3 Safety Interlocks Still Trip in Industrial Plants?
This article reviews Honeywell Safety Manager SIL3 SIS architecture, wiring and cabinet installation rules, PFDa...
-
How Does Poor Grounding Cause 4-20mA Signal Drift?