Skip to content
Automation parts, worldwide supply
Skip to product information
1 of 3

SKU:FS-SDOL-0424

Honeywell FC-SDOL-0424 Safe Loop-Monitored Output Module

In stock (14 units), ready to be shipped
  • Manufacturer: Honeywell

  • Product No.: FS-SDOL-0424

  • Product Type: Output Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 500g

  • Shipping port: Xiamen

  • Warranty: 12 months

30-Day Return Policy · 12-Month Warranty
  • Fast Delivery
  • 24/7 Support
  • Quality Assurance

Description

Honeywell FC-SDOL-0424 Safe Loop-Monitored Digital Output Module

The Honeywell FC-SDOL-0424 is a safe loop-monitored output module. It provides 4 channels at 24V DC with 1A capacity. This module includes lead breakage and short-circuit detection.

Technical Specifications

  • Brand & Model: Honeywell FC-SDOL-0424
  • Alternative PN: FS-SDOL-0424
  • Module Type: Safe Loop-Monitored Digital Output
  • Channel Count: 4 Output Channels
  • Output Voltage: 24 V DC
  • Output Current: 1 A per channel maximum
  • Max Load Power: 24 W per channel
  • Max Total Load: 3.6 A (module dissipation limit)
  • Voltage Drop: <1.3 V at 1 A
  • Off Current: <0.1 mA
  • Dimensions: 4 TE, 3 HE (4 HP, 3U)

Power Requirements

  • 5V DC Supply: 15 mA
  • 24V DC Internal: 50 mA
  • 24V DC External: 15 mA (without output load)
  • WDG Input Current: 4 mA

Load Specifications

  • Max Load Inductance: 0.5 H
  • Max Load Capacitance: 1 μF
  • Load Type: Resistive or inductive loads
  • Suppression Diodes: Built-in for inductive loads
  • Current Sense Drop: <1 V at 1 A
  • Output Type: Solid-state source, short-circuit proof

Frequently Asked Questions

How many channels and what current rating?

  • 4 channels at 24V DC, 1A per channel. Maximum total module load: 3.6A. Supports loads up to 24W per channel.

What monitoring features does it have?

  • Loop monitoring with lead breakage and short-circuit detection. Built-in suppression diodes for inductive loads. Fully tested safety functions.

What are the power requirements?

  • 5V DC: 15mA, 24V DC internal: 50mA, 24V DC external: 15mA (no load). WDG input current: 4mA. Compact 4HP, 3U design.
🏷️ Tags: Output Module
  • Orange
  • Black
  • DC-powered
  • Compact
  • Modular

Scalar (V/f)

Vector

AC-powered

  • Confirm the exact model, part number, and specifications before ordering.
  • Ensure compatibility with your current machinery or control systems.
  • Reach out via sale@etowonauto.com or +8617859788089 for technical assistance.
  • Review delivery options, lead times, and shipping requirements.
  • Follow manufacturer instructions and best practices during installation.

In-stock items are typically dispatched the same business day. For products not currently in stock, dispatch times may vary based on availability. International shipping is available, and shipping costs are calculated according to destination, weight, and carrier selection.

Returns are accepted within 30 days of receipt, provided items are unused and in original condition. Return shipping costs are the responsibility of the customer. Please contact us before returning any item to receive return authorization.

For more details, please review our Shipping & Return Policy.

View Product Details

ENSURE RELIABLE MACHINERY PERFORMANCE

Transform your home with the latest multi-electronics solutions, from intelligent lighting to vOptimize your operations with the Bently Nevada 3500 Monitoring System, offering real-time vibration and machinery condition monitoring to prevent failures and maximize uptime.oice-controlled devices all designed to make life easier, safer, and more connected.