FC-TSGAS-1624 Honeywell Gas Flame Detector Input Module | 24VDC

In stock (28 units), ready to be shipped
  • Manufacturer: Honeywell

  • Product No.: FC-TSGAS-1624

  • Product Type: Detector Input Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 2000g

  • Shipping port: Xiamen

  • Warranty: 12 months

30-Day Return Policy · 12-Month Warranty
  • Fast Delivery
  • 24/7 Support
  • Quality Assurance

Description

Honeywell TSGAS-1624 Safe Gas/Flame Detector Input FTA

The Honeywell TSGAS-1624 is a safe interface module for gas and flame detectors. It connects sixteen field signals to the SAI-1620m safety analog input modules. The module provides signal conversion and fused power distribution for your safety system.

Technical Specifications

  • Brand & Models: Honeywell, FS-TSGAS-1624, FC-TSGAS-1624
  • Function: Safe 16-channel interface for 0(4)-20 mA signals to SAI-1620m.
  • Input Channels: 16 analog inputs with common 0V.
  • Input Current: 0-25 mA range.
  • Input Resistance: 500 Ω (± 5%).
  • Power Supply: 24 V DC external, 3 mA (no load).
  • Output to SAI-1620m: 0-4 V DC, 0.1% accuracy.
  • Fuse per Channel: 500 mA (Schurter 0001.2501, 5x20 mm).
  • Dimensions: 225 × 70 × 60 mm / 8.86 × 2.76 × 2.36 in.
  • Terminals: Signal: 2.5 mm² max; Power (A,B): 16 mm² max.
  • Approvals: CE, TUV, UL, CSA, FM.

FAQ

  • Q: How does this module connect to the Safety Manager?
    A: The TSGAS-1624 uses a SICC-0001/Lx system interconnection cable to transfer signals to a redundant pair of SAI-1620m modules in the Safety Manager.
  • Q: What is the purpose of the internal fuses?
    A: Each channel has a 500 mA fuse to protect the connected field transmitter and the module's internal circuitry from overcurrent faults.
  • Q: Can it be used for non-safety applications?
    A: Yes, the TSGAS-1624 is suitable for both safety-related and standard process applications requiring reliable 0-20mA signal interfacing.
🏷️ Tags: Detector Input Module

Scalar (V/f)

Vector

AC-powered

  • Confirm the exact model, part number, and specifications before ordering.
  • Ensure compatibility with your current machinery or control systems.
  • Reach out via sale@etowonauto.com or +8617859788089 for technical assistance.
  • Review delivery options, lead times, and shipping requirements.
  • Follow manufacturer instructions and best practices during installation.

In-stock items are typically dispatched the same business day. For products not currently in stock, dispatch times may vary based on availability. International shipping is available, and shipping costs are calculated according to destination, weight, and carrier selection.

Returns are accepted within 30 days of receipt, provided items are unused and in original condition. Return shipping costs are the responsibility of the customer. Please contact us before returning any item to receive return authorization.

For more details, please review our Shipping & Return Policy.

View Product Details

ENSURE RELIABLE MACHINERY PERFORMANCE

Transform your home with the latest multi-electronics solutions, from intelligent lighting to vOptimize your operations with the Bently Nevada 3500 Monitoring System, offering real-time vibration and machinery condition monitoring to prevent failures and maximize uptime.oice-controlled devices all designed to make life easier, safer, and more connected.