Transformeer je huis met de nieuwste multi-elektronica oplossingen, van intelligente verlichting tot spraakgestuurde apparaten, allemaal ontworpen om het leven gemakkelijker, veiliger en meer verbonden te maken.
SKU:6ES7313-5BE00-0AB0
Siemens CPU 313C 6ES7313-5BE00-0AB0 S7-300 Compact Module
Manufacturer: Siemens
Product No.: 6ES7313-5BE00-0AB0
Product Type: CPU Module
Product Origin: DE
Payment:T/T, Western Union
Weight: 660g
Shipping port: Xiamen
Warranty: 12 months
Delen
- Snelle levering
- 24/7 Ondersteuning
- Kwaliteitsborging
Beschrijving
SIEMENS 6ES7313-5BE00-0AB0 SIMATIC S7-300 CPU 313C Compact CPU
The SIEMENS 6ES7313-5BE00-0AB0, also cataloged as the 6ES7313-5BE00-0AB0 CPU 313C, operates as a compact central processing unit with integrated digital and analog I/O, fast counters, and MPI communication executing user logic within SIMATIC S7-300 platforms.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 6ES7313-5BE00-0AB0 |
| Brand | Siemens |
| Product Type | CPU 313C Compact CPU |
| Series | SIMATIC S7-300 |
| Rated Supply Voltage | 24 VDC |
| Permissible Range | 20.4 V to 28.8 VDC |
| Current Consumption | 700 mA rated |
| Inrush Current | 11 A typ. |
| Power Loss | 14 W typ. |
| Work Memory | 32 kbyte integrated, not expandable |
| Load Memory | MMC expandable to 4 Mbyte |
| Bit Operation Time | 0.1 us typ., 0.2 us max |
| Word Operation Time | 0.5 us typ. |
| Fixed Point Arithmetic | 1 us typ. |
| Floating Point Arithmetic | 15 us typ. |
| Digital Inputs | 24 |
| Digital Outputs | 16 |
| Analog Inputs | 4 plus 1 Pt100 |
| Analog Outputs | 2 |
| Fast Counters | 3 at 30 kHz |
| Pulse Outputs | 3 at 2.5 kHz limit frequency |
| MPI Interface | 1 x MPI, 8 connections, 187.5 kbit/s max |
| Dimensions (W x H x D) | 120 mm x 125 mm x 130 mm |
| Weight | 660 g (approx.) |
Integrated I/O, Analog Channels, and Counter Functions
Unit weight is approximately 660 g with dimensions of 120 mm width, 125 mm height, and 130 mm depth. The CPU 313C integrates 24 digital inputs, 16 digital outputs, 4 analog inputs, 2 analog outputs, and 1 Pt100 resistance thermometer input. Three fast counters operate at 30 kHz with frequency measurement and PID controller functions. Three pulse outputs operate at a limit frequency of 2.5 kHz. Analog inputs support 0 to 10 V, 0 to 20 mA, +/-20 mA, 4 to 20 mA, Pt100, and 0 to 600 ohm ranges with 12-bit resolution and parameterizable integration times of 2.5, 16.6, or 20 ms. Analog outputs support 0 to 10 V, +/-10 V, 0 to 20 mA, +/-20 mA, and 4 to 20 mA with 12-bit resolution and 1 ms conversion time per channel. Basic error limit at 25 deg C is +/-0.7% for voltage and current, +/-3% for resistance and resistance thermometer. The hardware real-time clock is retentive and synchronizable. Up to 3 expansion units and 31 modules per rack are supported. Programming languages include LAD, FBD, STL, SCL, GRAPH, and HiGraph. Configuration requires STEP 7 V5.1 SP2 or higher.
Frequently Asked Questions
Q: What is the weight and physical size of the 6ES7313-5BE00-0AB0?
A: Approximately 660 g, with dimensions of 120 mm width, 125 mm height, and 130 mm depth.
Q: How many fast counters and pulse outputs does the CPU 313C support?
A: Three fast counters at 30 kHz with frequency measurement, and three pulse outputs at a 2.5 kHz limit frequency.
Q: What analog signal ranges does the CPU 313C accept?
A: Inputs support 0 to 10 V, 0 to 20 mA, +/-20 mA, 4 to 20 mA, Pt100, and 0 to 600 ohms. Outputs support 0 to 10 V, +/-10 V, 0 to 20 mA, +/-20 mA, and 4 to 20 mA.
Field Installation Guidelines
Install the CPU in slot 2 of the S7-300 rail and secure the mounting screws. Verify 24 VDC supply polarity before energizing the backplane. Insert a micro memory card before downloading the program. Confirm STEP 7 V5.1 SP2 or higher is used for configuration. Route shielded analog and counter cables to a maximum of 100 m for technological functions; unshielded cables are permitted only for standard inputs and outputs up to 600 m. Verify total output current per group does not exceed 8 A at up to 40 deg C or 4 A at up to 60 deg C. Verify potential separation groups of 16 and 8 for digital inputs and 8 for digital outputs.
Aanvullende specificaties
- DC-gevoed
- Modulair
Scalar (V/f)
Vector
Op netstroom
Koopgids
- Bevestig het exacte model, onderdeelnummer en specificaties voordat u bestelt.
- Zorg voor compatibiliteit met uw huidige machines of besturingssystemen.
- Neem contact op via sale@etowonauto.com of +8617859788089 voor technische ondersteuning.
- Bekijk de leveringsopties, doorlooptijden en verzendvereisten.
- Volg de instructies van de fabrikant en de beste praktijken tijdens de installatie.
Verzending en Retourneren
Voorraadartikelen worden doorgaans dezelfde werkdag verzonden. Voor producten die momenteel niet op voorraad zijn, kunnen de verzendtijden variëren afhankelijk van de beschikbaarheid. Internationale verzending is mogelijk, en de verzendkosten worden berekend op basis van bestemming, gewicht en gekozen vervoerder.
Retourzendingen worden geaccepteerd binnen 30 dagen na ontvangst, mits de artikelen ongebruikt en in originele staat zijn. De kosten voor retourzending zijn voor rekening van de klant. Neem alstublieft contact met ons op voordat u een artikel retourneert om een retourautorisatie te ontvangen.
Voor meer details kunt u onze Verzend- en Retourbeleid raadplegen.

3500/61-05-CN Temperature Monitor Module | Bently Nevada
3500/22-01-02-CN TDI Module Bently Nevada
Bently Nevada 3500/42-04-00 | Seismic Monitor
-
Snelle verzending
Originele onderdelen voor industriële automatisering beschikbaar voor snelle verzending wereldwijd.
-
Eenvoudige Retourzendingen
30 dagen retourrecht met 12 maanden garantie voor betrouwbare nazorgbescherming.
-
24/7 ondersteuning
Responsieve professionele ondersteuning om stabiele en efficiënte bedrijfsvoering te behouden.
-
Echt & Origineel
100% authentiek, rechtstreeks afkomstig van vertrouwde fabrikanten van industriële automatisering.
Technische & Koopgids
-
Troubleshoot Allen-Bradley PLC and ABB DCS Commissioning Faults?
Joint commissioning of Allen-Bradley PLC and ABB DCS systems demands rigorous signal mapping, layered diagnostics, an...
-
What Causes Packet Loss in DeltaV and ABB Fieldbus Networks?
This article explains how to optimize communication between Emerson DeltaV DCS and ABB fieldbus control modules ...
-
How Does Allen-Bradley Redundant PLC Improve DCS Safety?
This article explains how Allen-Bradley redundant PLC deployment supports petrochemical DCS safety control. It covers...
-
Can Mixed-Vendor PLCs Unite Without Full Replacement?
ABB industrial Ethernet modules translate protocols across Allen-Bradley, Siemens, and ABB PLC platforms in brownfiel...
-
How Do You Troubleshoot GE Fanuc PSU Failures?
This guide explains how field engineers can detect, diagnose, and prevent GE Fanuc power supply failures in legacy fa...
-
How Does Bently Nevada Transducer Replacement Cut Fan Downtime?
This article explains how to replace Bently Nevada vibration transducers on centrifugal fans without disrupting plant...