Beschrijving
Product Overview
The Siemens 6ES7455-0VS00-0AE0 is an FM 455 C control module for SIMATIC S7-400 systems, providing 16 continuous control channels. It combines 16 analog inputs, 16 digital inputs, and 16 analog outputs in a single module. Weighing approximately 1,400 g, this controller supports thermocouples, Pt100 resistance thermometers, and standard voltage/current signals for comprehensive process control.
Technical Configuration
This module operates from 24 V DC load voltage with a permissible range of 20.4 to 28.8 V. It draws a maximum of 440 mA (typical 370 mA) from load voltage without load. The 16 analog inputs accept thermocouples or 2-wire connections, while 8 channels support Pt100 or 4-wire connections. Integrated control technology provides 16 closed-loop controllers. Potential separation between channels and backplane bus uses optocouplers, tested at 500 V DC isolation.
Technical Specifications
| Parameter | Value |
|---|---|
| Manufacturer | Siemens |
| Part Number | 6ES7455-0VS00-0AE0 |
| Product Type | FM 455 C Control Module |
| Series | SIMATIC S7-400 |
| Control Channels | 16 continuous |
| Load Voltage | 24 V DC (20.4-28.8 V) |
| Current from L+ (No Load) | Max 440 mA, typ. 370 mA |
| Power Loss | Typ. 12 W, max 17.3 W |
| Digital Inputs | 16, 24 V DC (IEC 61131 type 2) |
| DI Signal "0" / "1" | -3 to +5 V / 13 to 30 V (7 mA typical) |
| Analog Inputs | 16 (8 with Pt100/4-wire) |
| Voltage Input Ranges | 0 to +10 V, -1.75 to +11.75 V, -80 to +80 mV |
| Current Input Ranges | 0-20 mA, 0-23.5 mA, -3.5 to +23.5 mA, 4-20 mA |
| Thermocouple Types | B, J, K, R, S |
| RTD Type | Pt100 |
| Analog Outputs | 16 |
| Voltage Output Ranges | 0-10 V, -10 to +10 V |
| Current Output Ranges | 0-20 mA, -20 to +20 mA, 4-20 mA |
| Voltage Output Load | Min 1 kΩ, max 1 µF capacitive |
| Current Output Load | Max 500 Ω, max 1 mH inductive |
| Resolution | 12 or 14 bit, parameterizable |
| Settling Time | 0.1 ms resistive, 3.3 ms capacitive, 0.5 ms inductive |
| Closed-Loop Controllers | 16 |
| Isolation Tested | 500 V DC |
| Dimensions (W x H x D) | 50 x 290 x 210 mm |
| Weight | Approx. 1,400 g |
| Front Connector | 2 x 48-pin required |
Installation Guide
Install the FM 455 C module in a compatible S7-400 rack slot and secure both 48-pin front connectors. Connect 24 V DC load voltage within the 20.4-28.8 V range. Use shielded cable for analog signals with maximum 200 m length (50 m for 80 mV and thermocouple inputs). Verify voltage output loads meet minimum 1 kΩ and current output loads remain below 500 Ω. Internal or external Pt100 temperature compensation is parameterizable for thermocouple measurements.
Engineering Advantages
This module integrates 16 closed-loop controllers with 16 AI, 16 DI, and 16 AO in a single unit, reducing rack space and wiring. Support for thermocouples, Pt100 RTDs, and standard voltage/current signals provides exceptional measurement flexibility. Parameterizable 12-bit or 14-bit resolution suits both standard and high-precision applications. Optocoupler isolation between channels and backplane bus protects the system from field transients. Short-circuit-protected voltage outputs with 25 mA limit safeguard connected actuators.
Technical FAQs
Q1: How many control loops does the 6ES7455-0VS00-0AE0 support?
A1: This module integrates 16 closed-loop controllers with 16 analog inputs, 16 digital inputs, and 16 analog outputs.
Q2: What temperature sensor types does this module accept?
A2: It accepts thermocouple types B, J, K, R, and S, plus Pt100 resistance thermometers with parameterizable internal or external compensation.
Q3: What are the analog output load requirements?
A3: Voltage outputs require minimum 1 kΩ load (max 1 µF capacitive), while current outputs accept maximum 500 Ω load (max 1 mH inductive).
Aanvullende specificaties
Scalar (V/f)
Vector
Op netstroom
Koopgids
- Bevestig het exacte model, onderdeelnummer en specificaties voordat u bestelt.
- Zorg voor compatibiliteit met uw huidige machines of besturingssystemen.
- Neem contact op via sale@etowonauto.com of +8617859788089 voor technische ondersteuning.
- Bekijk de leveringsopties, doorlooptijden en verzendvereisten.
- Volg de instructies van de fabrikant en de beste praktijken tijdens de installatie.
Verzending en Retourneren
Voorraadartikelen worden doorgaans dezelfde werkdag verzonden. Voor producten die momenteel niet op voorraad zijn, kunnen de verzendtijden variëren afhankelijk van de beschikbaarheid. Internationale verzending is mogelijk, en de verzendkosten worden berekend op basis van bestemming, gewicht en gekozen vervoerder.
Retourzendingen worden geaccepteerd binnen 30 dagen na ontvangst, mits de artikelen ongebruikt en in originele staat zijn. De kosten voor retourzending zijn voor rekening van de klant. Neem alstublieft contact met ons op voordat u een artikel retourneert om een retourautorisatie te ontvangen.
Voor meer details kunt u onze Verzend- en Retourbeleid raadplegen.

3500/61-05-CN Temperature Monitor Module | Bently Nevada
3500/22-01-02-CN TDI Module Bently Nevada
Bently Nevada 3500/42-04-00 | Seismic Monitor
-
Snelle verzending
Originele onderdelen voor industriële automatisering beschikbaar voor snelle verzending wereldwijd.
-
Eenvoudige Retourzendingen
30 dagen retourrecht met 12 maanden garantie voor betrouwbare nazorgbescherming.
-
24/7 ondersteuning
Responsieve professionele ondersteuning om stabiele en efficiënte bedrijfsvoering te behouden.
-
Echt & Origineel
100% authentiek, rechtstreeks afkomstig van vertrouwde fabrikanten van industriële automatisering.
Technische & Koopgids
-
How Does Siemens ET200SP Simplify PLC and DCS Integration?
This article explains Siemens ET200SP distributed remote I/O hardware sizing, DIN rail installation, field wirin...
-
How Do GE IC695 RX3i I/O Modules Work?
This article explains GE IC695 RX3i I/O module specifications, compatibility validation, field installation proc...
-
What Is Emerson DeltaV Virtual DCS and How Does It Work?
Emerson DeltaV Virtual DCS replicates full distributed control system behavior using identical runtime binaries, enab...
-
How to Commission Siemens PCS 7 OS for DCS Plants?
This article explains how to commission, troubleshoot and tune Siemens PCS 7 OS operator stations for distribute...
-
Is Compact DCS Better Than PLC for Small Plants?
This article examines the ABB AC700F Freelance DCS as a compact control solution for small batch process plants ...
-
What Makes ControlEdge UCD Ideal for Water Treatment DCS?
Honeywell ControlEdge UCD DCS delivers DCS-grade reliability in a compact, PLC-like footprint suited to mid-size muni...