Transformeer je huis met de nieuwste multi-elektronica oplossingen, van intelligente verlichting tot spraakgestuurde apparaten, allemaal ontworpen om het leven gemakkelijker, veiliger en meer verbonden te maken.
SKU:ATV71HC11N4D
Schneider Variable Speed Drive 215A | ATV71HC11N4D
Manufacturer: Schneider
Product No.: ATV71HC11N4D
Product Type: Variable Speed Drive
Product Origin: FR
Payment:T/T, Western Union
Weight: 90000g
Shipping port: Xiamen
Warranty: 12 months
Delen
- Snelle levering
- 24/7 Ondersteuning
- Kwaliteitsborging
Beschrijving
Schneider Electric ATV71HC11N4D Altivar 71 Variable Speed Drive
Schneider Electric ATV71HC11N4D | Altivar 71 variable speed drive for complex, high-power machines. Delivers 110 kW (150 HP) motor power with 215 A nominal output current at 380-480V three-phase supply. Integrated EMC filter and heat sink. Reinforced version without DC choke, designed for door mounting. Supports asynchronous and synchronous motors. Weight: 90 kg (198.4 lbs).
Technical Specifications
| Manufacturer | Schneider Electric |
| Part Number | ATV71HC11N4D |
| Product Line | Altivar 71 |
| Product Type | Variable Speed Drive |
| Motor Power | 110 kW (150 HP), 3-phase 380-480V |
| Supply Voltage | 380-480V (-15%/+10%), 3-phase |
| Supply Voltage Limits | 323-528V |
| Supply Frequency | 50-60 Hz ±5% (47.5-63 Hz) |
| Line Current (480V) | 163 A |
| Line Current (380V) | 202 A |
| Apparent Power | 133 kVA @ 380V |
| Nominal Output Current | 215 A @ 2.5 kHz |
| Maximum Transient Current | 323 A for 60 s; 355 A for 2 s |
| Output Frequency | 0.1-500 Hz |
| Nominal Switching Frequency | 2.5 kHz (adjustable 2.5-8 kHz) |
| Prospective Line Isc | 35 kA |
| EMC Filter | Integrated |
| Heat Sink | Yes |
| Variant | Reinforced version, without DC choke |
| Mounting Type | Door Mount |
| Control Methods | Sensorless Vector, Vector, V/f, Synchronous |
| Braking to Standstill | DC injection |
| Analog Inputs | 2 (AI1 ±10V, AI2 0-20mA/0-10V) |
| Analog Output | 1 (AO1 0-20mA/0-10V) |
| Discrete Inputs | 7 (LI1-LI5 programmable 24VDC, LI6 configurable, PWR safety) |
| Discrete Outputs | 2 relay (R1 NO/NC, R2 NO) |
| Communication | Modbus (2-wire RS485), CANopen |
| Transmission Rates (Modbus) | 4800, 9600, 19200, 38.4 kbps |
| Transmission Rates (CANopen) | 20 kbps to 1 Mbps |
| Speed Accuracy (Closed-Loop) | ±0.01% of nominal speed |
| Torque Accuracy (Closed-Loop) | ±5% |
| Transient Overtorque | 170% for 60 s; 220% for 2 s |
| Braking Torque (with resistor) | ≤150% |
| Insulation Resistance | >1 MOhm at 500V DC for 1 minute |
| Dielectric Strength | 3535V DC (earth to power); 5092V DC (control to power) |
| Protection Class | IP54 (lower), IP41 (upper), IP30 (front/sides), IP00 |
| Noise Level | 69.5 dB (86/188/EEC) |
| Operating Temperature | -10°C to +50°C (without derating) |
| Storage Temperature | -25°C to +70°C |
| Relative Humidity | 5-95% (non-condensing) |
| Operating Altitude | ≤1000 m without derating; 1000-3000 m with 1% derating per 100 m |
| Vibration Resistance | 0.6 gn (10-200 Hz); 1.5 mm peak-to-peak (3-10 Hz) |
| Shock Resistance | 7 gn, 11 ms (EN/IEC 60068-2-27) |
| Dimensions (H x W x D) | 1022 x 360 x 377 mm (40.2 x 14.2 x 14.8 in) |
| Net Weight | 90 kg (198.4 lbs) |
| Gross Weight | 121.56 kg (268.00 lbs) |
| Standards | EN/IEC 61800-3, EN/IEC 61800-5-1, UL Type 1 |
| Certifications | CE, UL, CSA, GOST, NOM 117, C-tick |
Additional Technical Parameters
| Maximum Motor Cable Length (Shielded) | 100 m (328.08 ft) |
| Maximum Motor Cable Length (Unshielded) | 200 m (656.2 ft) |
| Analog Input Sampling Time | 2 ms ±0.5 ms |
| Discrete Input Sampling Time | 2 ms ±0.5 ms |
| STO Response Time | ≤100 ms |
| Relay Output Response Time | 7 ms ±0.5 ms |
| Analog Input Linearity Error | ±0.15% of maximum value |
| Analog Output Linearity Error | ±0.2% |
| Relay Mechanical Life | 100,000 cycles |
| Minimum Switching Current | 3 mA at 24V DC |
Installation Notes
Mount vertically (±10°) using door-mount configuration. Connect 380-480V three-phase supply per local electrical codes. Observe terminal tightening torques: 0.6 N·m for control terminals, 24 N·m for motor terminals, 12 N·m for PA/PB, 41 N·m for PC/PO/PA/+. Maximum motor cable length is 100 m shielded or 200 m unshielded. Maintain operating temperature within -10°C to +50°C without derating. For altitudes above 1000 m, apply 1% current derating per 100 m. The D suffix indicates no DC choke and no graphic terminal. Ensure proper grounding and use the integrated EMC filter for electromagnetic compliance.
FAQs
Q1: What is the motor power rating of this drive?
A1: 110 kW (150 HP) at 380-480V three-phase supply.
Q2: What communication protocols are built in?
A2: Modbus (2-wire RS485) and CANopen.
Q3: What does the D suffix indicate?
A3: The drive is a reinforced version without a DC choke and without a remote graphic terminal.
Aanvullende specificaties
Scalar (V/f)
Vector
Op netstroom
Koopgids
- Bevestig het exacte model, onderdeelnummer en specificaties voordat u bestelt.
- Zorg voor compatibiliteit met uw huidige machines of besturingssystemen.
- Neem contact op via sale@etowonauto.com of +8617859788089 voor technische ondersteuning.
- Bekijk de leveringsopties, doorlooptijden en verzendvereisten.
- Volg de instructies van de fabrikant en de beste praktijken tijdens de installatie.
Verzending en Retourneren
Voorraadartikelen worden doorgaans dezelfde werkdag verzonden. Voor producten die momenteel niet op voorraad zijn, kunnen de verzendtijden variëren afhankelijk van de beschikbaarheid. Internationale verzending is mogelijk, en de verzendkosten worden berekend op basis van bestemming, gewicht en gekozen vervoerder.
Retourzendingen worden geaccepteerd binnen 30 dagen na ontvangst, mits de artikelen ongebruikt en in originele staat zijn. De kosten voor retourzending zijn voor rekening van de klant. Neem alstublieft contact met ons op voordat u een artikel retourneert om een retourautorisatie te ontvangen.
Voor meer details kunt u onze Verzend- en Retourbeleid raadplegen.

3500/61-05-CN Temperature Monitor Module | Bently Nevada
3500/22-01-02-CN TDI Module Bently Nevada
Bently Nevada 3500/42-04-00 | Seismic Monitor
-
Snelle verzending
Originele onderdelen voor industriële automatisering beschikbaar voor snelle verzending wereldwijd.
-
Eenvoudige Retourzendingen
30 dagen retourrecht met 12 maanden garantie voor betrouwbare nazorgbescherming.
-
24/7 ondersteuning
Responsieve professionele ondersteuning om stabiele en efficiënte bedrijfsvoering te behouden.
-
Echt & Origineel
100% authentiek, rechtstreeks afkomstig van vertrouwde fabrikanten van industriële automatisering.
Technische & Koopgids
-
How Does the Bently Nevada 3500/42M Vibration Module Drift?
This technical guide examines the Bently Nevada 3500/42M vibration module within industrial automation architect...
-
What Causes IC694MDL Fault Codes in GE RX3i PLC Systems?
This guide explains GE RX3i IC694MDL discrete I/O fault codes, key electrical parameters, ESD and torque requirements...
-
What CFC Rules Cut PCS7 Batch Abort Rates Fast?
This article presents enforceable CFC programming governance rules for Siemens PCS7 DCS batch plants, covering b...
-
What Makes the 1769-L3ER Ideal for Compact Skid Automation?
This guide explains how the Allen-Bradley 1769 CompactLogix L3ER bridges the gap between micro PLCs and large DC...
-
Why Do SIL3 Safety Interlocks Still Trip in Industrial Plants?
This article reviews Honeywell Safety Manager SIL3 SIS architecture, wiring and cabinet installation rules, PFDa...
-
How Does Poor Grounding Cause 4-20mA Signal Drift?
This guide explains how MTL signal isolators fail through distortion, drift and EMI in PLC and DCS loops, then d...