MTL5041 Repeater Power Supply

The MTL5041 from MTL Instruments provides a fully-floating DC supply for 2-wire transmitters in hazardous areas. This single-channel unit energizes transmitters located in Zone 0 while repeating the current signal to drive safe-area loads. It delivers fast, accurate signal repetition with complete electrical isolation.

Key Technical Specifications

  • Brand: MTL Instruments
  • Model: MTL5041
  • Product Type: Repeater Power Supply
  • Channels: One channel
  • Transmitter Type: 2-wire 4-20mA conventional
  • Response Time: 250µs to 10% of final value
  • Supply Voltage: 20 to 35V DC

Hazardous Area Certification

  • Transmitter Location: Zone 0, IIC, T4-T6 hazardous area
  • Division Rating: Division 1, Group A hazardous location
  • The MTL5041 maintains intrinsic safety standards
  • It provides safe operation for transmitters in explosive atmospheres

Input Specifications

  • Signal Range: 0 to 24mA including over-range
  • Transmitter Voltage: 16.5V at 20mA
  • Input Terminals: Terminal 1 (Input –ve), Terminal 2 (Input +ve)
  • The unit provides floating DC supply for 2-wire transmitters

Output Performance

  • Signal Range: 4 to 20mA standard output
  • Extended Range: 0 to 24mA over/under-range
  • Load Resistance: 0 to 1kΩ maximum
  • Output Resistance: >2MΩ
  • Output Terminals: Terminal 11 (Output –ve), Terminal 12 (Output +ve)

Accuracy & Speed

  • Transfer Accuracy: Better than 20µA at 20°C
  • Typical Accuracy: Typically 5µA
  • Temperature Drift: <1µA/°C
  • Response Time: Settles within 250µs to 10% of final value
  • Circuit Ripple: <125µA peak-to-peak

Power Requirements

  • Supply Voltage: 20 to 35V DC
  • Supply Terminals: Terminal 13 (Supply –ve), Terminal 14 (Supply +ve)
  • Current Consumption: 70mA at 24V with 20mA signal
  • Power Dissipation: 1.2W at 24V maximum
  • Status Indicator: Green LED for power monitoring

Safety Parameters

  • Safety Voltage: 28V maximum
  • Internal Resistance: 300Ω
  • Safety Current: 93mA maximum
  • Isolation Voltage: Um = 250V rms or DC

Frequently Asked Questions

  • What transmitter voltage does the MTL5041 provide?
    It delivers 16.5V at 20mA for powering 2-wire transmitters.
  • What is the maximum load resistance?
    The output can drive safe-area loads up to 1kΩ.
  • How fast is the response time?
    It settles to within 10% of final value within 250 microseconds.
  • What areas is it certified for?
    It is certified for Zone 0, IIC, T4-T6 and Division 1, Group A areas.
🏷️ Tags: Repeater Power Supply

Scalar (V/f)

Vector

AC-powered

  • Confirm the exact model, part number, and specifications before ordering.
  • Ensure compatibility with your current machinery or control systems.
  • Reach out via sale@etowonauto.com or +8617859788089 for technical assistance.
  • Review delivery options, lead times, and shipping requirements.
  • Follow manufacturer instructions and best practices during installation.

In-stock items are typically dispatched the same business day. For products not currently in stock, dispatch times may vary based on availability. International shipping is available, and shipping costs are calculated according to destination, weight, and carrier selection.

Returns are accepted within 30 days of receipt, provided items are unused and in original condition. Return shipping costs are the responsibility of the customer. Please contact us before returning any item to receive return authorization.

For more details, please review our Shipping & Return Policy.

View Product Details

ENSURE RELIABLE MACHINERY PERFORMANCE

Transform your home with the latest multi-electronics solutions, from intelligent lighting to vOptimize your operations with the Bently Nevada 3500 Monitoring System, offering real-time vibration and machinery condition monitoring to prevent failures and maximize uptime.oice-controlled devices all designed to make life easier, safer, and more connected.