Tsallake zuwa abun ciki
Kayan aikin sarrafa kansu, isarwa a ko’ina cikin duniya
Tsallaka zuwa bayanin kaya
1 na 3

SKU:6ES7455-1VS00-0AE0

6ES7455-1VS00-0AE0 Siemens | FM 455 S Step and Pulse

A kan haja (24 guda), a shirye don aikawa
  • Manufacturer: Siemens

  • Product No.: 6ES7455-1VS00-0AE0

  • Product Type: Control Module

  • Product Origin: DE

  • Payment:T/T, Western Union

  • Weight: 1400g

  • Shipping port: Xiamen

  • Warranty: 12 months

Dokar Mayar da Kaya na Kwanaki 30 · Garantin Watanni 12
  • Isarwa Cikin Gaggawa
  • Tallafi na awa 24 a rana, kwana 7 a mako
  • Tabbacin Inganci

Bayani

Product Overview

The Siemens 6ES7455-1VS00-0AE0 is an FM 455 S control module for SIMATIC S7-400 systems, providing 16 step and pulse control channels. It combines 16 analog inputs, 16 digital inputs, and 32 digital outputs in a single module. Weighing approximately 1,400 g, this controller supports thermocouples, Pt100 resistance thermometers, and standard signals for comprehensive process control with pulse output capability.

Technical Configuration

This module operates from 24 V DC load voltage with a permissible range of 20.4 to 28.8 V. It draws a maximum of 400 mA (typical 330 mA) from load voltage without load. The 16 analog inputs accept thermocouples or 2-wire connections, while 8 channels support Pt100 or 4-wire connections. The 32 digital outputs feature electronic short-circuit protection and inductive shutdown voltage limitation to L+ (-1.5 V). Potential separation between channels and backplane bus uses optocouplers, tested at 500 V DC isolation.

Technical Specifications

Parameter Value
Manufacturer Siemens
Part Number 6ES7455-1VS00-0AE0
Product Type FM 455 S Control Module
Series SIMATIC S7-400
Control Channels 16 step and pulse
Load Voltage 24 V DC (20.4-28.8 V)
Current from L+ (No Load) Max 400 mA, typ. 330 mA
Power Loss Typ. 10.7 W, max 16.2 W
Digital Inputs 16, 24 V DC (IEC 61131 type 2)
DI Signal "0" / "1" -3 to +5 V / 13 to 30 V (7 mA typical)
Digital Outputs 32, electronic short-circuit protection
Output Current (Rated) 0.1 A (5-150 mA range, 0-60 °C)
Load Resistance Range 240 Ω to 4 kΩ
Lamp Load Max 5 W
Switching Frequency Max 100 Hz resistive/lamps, 0.5 Hz inductive
Analog Inputs 16 (8 with Pt100/4-wire)
Voltage Input Ranges 0 to +10 V, -1.75 to +11.75 V, -80 to +80 mV
Current Input Ranges 0-20 mA, 0-23.5 mA, -3.5 to +23.5 mA, 4-20 mA
Thermocouple Types B, J, K, R, S
RTD Type Pt100
Resolution 12 or 14 bit, parameterizable
Closed-Loop Controllers 16
Isolation Tested 500 V DC
Dimensions (W x H x D) 50 x 290 x 210 mm
Weight Approx. 1,400 g
Front Connector 2 x 48-pin required

Installation Guide

Install the FM 455 S module in a compatible S7-400 rack slot and secure both 48-pin front connectors. Connect 24 V DC load voltage within the 20.4-28.8 V range. Use shielded cable for analog signals with maximum 200 m length (50 m for 80 mV and thermocouple inputs). Verify digital output loads fall within the 240 Ω to 4 kΩ resistance range. Internal or external Pt100 temperature compensation is parameterizable for thermocouple measurements.

Engineering Advantages

This module integrates 16 closed-loop controllers with 16 AI, 16 DI, and 32 DO in a single unit, combining step/pulse control with analog measurement. The 32 digital outputs provide twice the output density of the FM 455 C, reducing module count in high-channel applications. Electronic short-circuit protection and inductive shutdown voltage limitation safeguard connected loads. Parameterizable 12-bit or 14-bit resolution suits both standard and precision measurement tasks. Optocoupler isolation between channels and backplane bus protects the system from field transients.

Technical FAQs

Q1: How many digital outputs does the 6ES7455-1VS00-0AE0 provide?
A1: This FM 455 S module provides 32 digital outputs with electronic short-circuit protection, plus 16 analog inputs, 16 digital inputs, and 16 closed-loop controllers.

Q2: What is the digital output load resistance range?
A2: Digital outputs operate with load resistance from 240 Ω to 4 kΩ, with rated output current of 0.1 A (5-150 mA range at 0-60 °C).

Q3: What temperature sensor types does this module accept?
A3: It accepts thermocouple types B, J, K, R, and S, plus Pt100 resistance thermometers with parameterizable internal or external compensation.

🏷️ Tags: Control Module Siemens

Sikeli (V/f)

Vector

mai amfani da wutar AC

  • Tabbatar da ainihin samfurin, lambar ɓangare, da ƙayyadaddun bayanai kafin yin oda.
  • Tabbatar da jituwa da injin ko tsarin kula da kake amfani da su a yanzu.
  • Tuntuɓe mu ta sale@etowonauto.com ko +8617859788089 don taimakon fasaha.
  • Duba zaɓuɓɓukan isarwa, lokacin jagora, da buƙatun jigilar kaya.
  • Bi umarnin masana’anta da mafi kyawun hanyoyin aiki yayin girkawa.

Kayayyakin da ke cikin sito yawanci ana tura su a cikin wannan ranar aikin. Ga kayayyakin da ba sa cikin sito a yanzu, lokacin tura su na iya bambanta bisa ga samuwa. Ana ba da jigilar kaya zuwa ƙasashen waje, kuma ana ƙididdige kuɗin jigila bisa wurin da ake aikawa, nauyi, da kamfanin sufuri da aka zaɓa.

Ana karɓar mayar da kaya cikin kwanaki 30 bayan karɓa, muddin kayan ba a yi amfani da su ba kuma suna cikin yanayin da suka fito daga masana’anta. Kuɗin jigilar mayar da kaya nauyi ne a kan abokin ciniki. Da fatan za a tuntube mu kafin ku mayar da duk wani kaya domin samun izinin mayarwa.

Don ƙarin bayani, don Allah ku duba Manufar Jigila & Mayar da Kaya.

Duba bayanin samfur

TABBTAR DA INGANTACCEN AIKIN NA'URORI

Canza gidanka da sabbin hanyoyin na’urorin lantarki masu yawa, daga hasken wuta mai hankali zuwa inganta ayyukanka da Bently Nevada 3500 Monitoring System, wanda ke ba da sa ido a ainihin lokaci kan girgiza da yanayin na’urorin injina don hana gazawa da ƙara lokacin aiki, da na’urorin da ake sarrafa su da murya duk an ƙera su ne don sauƙaƙa rayuwa, ƙara tsaro, da ƙarfafa haɗin kai.