Canza gidanka da sabbin hanyoyin na’urorin lantarki masu yawa, daga hasken wuta mai hankali zuwa inganta ayyukanka da Bently Nevada 3500 Monitoring System, wanda ke ba da sa ido a ainihin lokaci kan girgiza da yanayin na’urorin injina don hana gazawa da ƙara lokacin aiki, da na’urorin da ake sarrafa su da murya duk an ƙera su ne don sauƙaƙa rayuwa, ƙara tsaro, da ƙarfafa haɗin kai.
SKU:3500/53-02-00
3500/53-02-00 Bently Nevada Overspeed Detection System
Manufacturer: Bently Nevada
Product No.: 3500/53-02-00
Product Type: Temperature Monitor
Product Origin: USA
Payment:T/T, Western Union
Weight: 450g
Shipping port: Xiamen
Warranty: 12 months
Raba
- Isarwa Cikin Gaggawa
- Tallafi na awa 24 a rana, kwana 7 a mako
- Tabbacin Inganci
Bayani
Product Overview
The 3500/53-02-00 is a two-channel electronic overspeed detection system for turbines and compressors. It accepts proximity probe or magnetic pickup signals. Modules combine for 2-out-of-2 or 2-out-of-3 (recommended) voting, ensuring fail-safe operation in the 3500 rack.
Technical Configuration
Channel Option: 02 – Two Channel System
The 02 suffix designates a two-channel module. Each channel accepts one transducer input. Multiple modules combine for voting architectures.
Agency Approval: 00 – None
Standard version without hazardous area certifications. Complies with FCC, EMC, LV, and RoHS. For Class I, Div 2, order CSA/NRTL/C option (01).
Technical Specifications
| Parameter | Specification |
|---|---|
| Channels | 2 per module |
| Input Signal | +10.0 V to -24.0 V (internal limiting) |
| Input Impedance | 20 kΩ |
| Transducer Power | -24 Vdc, 40 mA max |
| Recorder Output | +4 to +20 mA (proportional to rpm) |
| Recorder Resolution | 0.3662 µA/bit ±0.25% @ RT, ±0.7% over temp |
| Load Resistance | 0 to 600 Ω |
| Relay Type | SPDT, epoxy sealed, arc suppressers |
| Max Relay Power | 120 W (dc) / 600 VA (ac) |
| Max Relay Current | 5 A (resistive) |
| Max Relay Voltage | 30 Vdc / 250 Vac |
| Contact Life | 100,000 @ 5A, 24Vdc or 120Vac |
| Power Consumption | 8.0 W typical |
| Operating Temperature | -30°C to +65°C (-22°F to +149°F) |
| Storage Temperature | -40°C to +85°C (-40°F to +185°F) |
| Humidity | 95% non-condensing |
| Monitor Module (H x W x D) | 241.3 mm x 24.4 mm x 241.8 mm |
| Monitor Weight | 0.82 kg (1.8 lbs) |
| I/O Module (H x W x D) | 241.3 mm x 24.4 mm x 99.1 mm |
| I/O Weight | 0.45 kg (1.0 lbs) |
Installation & Maintenance
Wiring
Connect probes or pickups to I/O inputs. Use shielded twisted-pair cables. Front panel provides buffered output (coaxial, 550Ω) for diagnostics – short-circuit and ESD protected.
Configuration
Set overspeed setpoints and voting logic via 3500 Configuration Software. Use three modules for 2-out-of-3 voting. Relays selectable for Normally Energized or De-energized.
Hazardous Area
For Class I, Div 2 (Groups A-D), order CSA/NRTL/C option (01) – T4 at Ta = -20°C to +65°C. Standard (00) for general industrial use.
Engineering Advantages
Redundant Voting Architecture
2-out-of-3 voting provides exceptional reliability. System trips only when two modules detect overspeed – remains functional with one module failure.
Robust Relays
Epoxy-sealed SPDT relays with arc suppressers. 100,000 operations at 5A, 24Vdc or 120Vac ensures long-term durability.
Wide Compatibility
Operates -30°C to +65°C, 95% humidity. -24Vdc supply and 20kΩ input support both proximity probes and magnetic pickups.
Technical FAQs
Q1: Recommended voting configuration?
A1: 2-out-of-3 using three 3500/53 modules. System trips only when at least two detect overspeed.
Q2: Is recorder output short-circuit protected?
A2: Yes. +4 to +20 mA output is protected. Operation unaffected by shorts. Load: 0 to 600Ω.
Q3: Difference between 02 and other channel options?
A3: 02 = two-channel module. Multiple modules required for voting – channel option does not affect voting capability.
Ƙarin ƙayyadaddun bayanai
- Shuɗi
Sikeli (V/f)
Vector
mai amfani da wutar AC
Jagorar Sayi
- Tabbatar da ainihin samfurin, lambar ɓangare, da ƙayyadaddun bayanai kafin yin oda.
- Tabbatar da jituwa da injin ko tsarin kula da kake amfani da su a yanzu.
- Tuntuɓe mu ta sale@etowonauto.com ko +8617859788089 don taimakon fasaha.
- Duba zaɓuɓɓukan isarwa, lokacin jagora, da buƙatun jigilar kaya.
- Bi umarnin masana’anta da mafi kyawun hanyoyin aiki yayin girkawa.
Isarwa da Mayar da Kaya
Kayayyakin da ke cikin sito yawanci ana tura su a cikin wannan ranar aikin. Ga kayayyakin da ba sa cikin sito a yanzu, lokacin tura su na iya bambanta bisa ga samuwa. Ana ba da jigilar kaya zuwa ƙasashen waje, kuma ana ƙididdige kuɗin jigila bisa wurin da ake aikawa, nauyi, da kamfanin sufuri da aka zaɓa.
Ana karɓar mayar da kaya cikin kwanaki 30 bayan karɓa, muddin kayan ba a yi amfani da su ba kuma suna cikin yanayin da suka fito daga masana’anta. Kuɗin jigilar mayar da kaya nauyi ne a kan abokin ciniki. Da fatan za a tuntube mu kafin ku mayar da duk wani kaya domin samun izinin mayarwa.
Don ƙarin bayani, don Allah ku duba Manufar Jigila & Mayar da Kaya.

3500/61-05-CN Temperature Monitor Module | Bently Nevada
3500/22-01-02-CN TDI Module Bently Nevada
Bently Nevada 3500/42-04-00 | Seismic Monitor
-
Isarwa cikin gaggawa
Sassan kayan otomeshan na masana’antu na ainihi suna nan a shirye don aikawa cikin gaggawa a ko’ina cikin duniya.
-
Mayar da kaya cikin sauƙi
Tallafin mayar da kaya na kwanaki 30 tare da garantin watanni 12 don tabbatacciyar kariya bayan saye.
-
Taimako a kowane lokaci (24/7)
Tallafin ƙwararru mai saurin amsawa don taimakawa kiyaye ayyuka cikin kwanciyar hankali da inganci.
-
Na Gaskiya & Asali
Kashi 100% na asali ne, ana samar da su kai tsaye daga amintattun masana’antun kayan sarrafa masana’antu.
Jagorar Fasaha da Siyarwa
-
How Does TSI Integration Reduce Turbine False Trip Risks?
This article examines data-driven turbine safety monitoring and mechanical fault diagnosis within industrial automati...
-
Can turn-key automation services really cut plant downtime by 47%?
This article examines how fragmented PLC, DCS, TSI, and power-protection systems drive hidden operational losses in p...
-
Is Your Manufacturing Execution Still Stuck in Open-Loop Mode?
This article examines how closed-loop automated control resolves the critical disconnect between production planning ...
-
Can Predictive Analytics Cut Factory Automation Downtime?
This article examines how predictive abnormality pre-judgment technology addresses the economic burden of reactive fa...
-
Is Full PLC Replacement Best for Brown-Field Automation?
This technical article analyzes the hidden costs of full-scale PLC and DCS hardware replacement in brown-field plants...
-
Is Your DCS Logic Tuning Ready for Real-World Production Loads?
This article examines the critical role of physical on-site commissioning and logic tuning in industrial automation, ...