Honeywell FS-TSDI-1624C 24V Safety Input FTA

Solo 8 unità rimaste
  • Manufacturer: Honeywell

  • Product No.: FS-TSDI-1624C

  • Product Type: Input Module

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 200g

  • Shipping port: Xiamen

  • Warranty: 12 months

Politica di reso di 30 giorni · Garanzia di 12 mesi
  • Consegna Veloce
  • Assistenza 24 ore su 24, 7 giorni su 7
  • Assicurazione della qualità

Descrizione

Product Overview

The FS-TSDI-1624C is a high-reliability Field Termination Assembly (FTA) module designed to interface between field wiring and the Honeywell Safety Manager system. This module provides 16 current-limited digital input channels specifically approved for routing non-incendive field circuits into Class I, Division 2 hazardous locations. 

Core Technical Advantages

Class I, Division 2 Hazardous Location Safety

Engineered with precise energy-limiting circuitry, this module restricts igniting current to less than 100 mA per channel under worst-case voltage conditions. This design allows direct interfacing with field devices located in explosive gas atmospheres without the need for additional bulky intrinsic safety barriers.

Dual-Group Fuse Protection

The 16 channels are divided into two isolated groups of 8. Each group features a high-voltage rated 250 mA SOC SHV12 ceramic fuse on the common positive line, preventing field-side short circuits from disabling the entire module and isolating faults effectively.

Redundant Module Compatibility

The hardware architecture natively accepts dual connection paths, allowing a single FTA block to drive a redundant pair of safety input cards simultaneously. This architecture eliminates single points of failure between the field termination and the safety logic layer.

Technical Specifications

Parameter Specification Details
Manufacturer Honeywell (Safety Manager)
Model Type FS-TSDI-1624C / FC-TSDI-1624C
Channel Configuration 16 Channels (2 Groups of 8)
Nominal Input Voltage 24 V DC (-15% to +30%)
Input Current Load ≤ 15 mA at 24 V DC (with Redundant Load)
Igniting Current Limit < 100 mA at 24 V DC +30% (per channel)
Fuse Rating / Model 250 mA, 400 V AC/DC (SOC SHV12)
Dimensions (L × W × H) 170 × 70 × 60 mm (6.69 × 2.76 × 2.36 in)

Class I Division 2 Loop Parameter Limits

To preserve non-incendive loop integrity, interconnected field wiring must comply strictly with the following electrical constraints:

  • Max. Closed Loop Resistance: 250 Ω
  • Min. Open Loop Resistance: 15 kΩ
  • Hydrogen Environments (Group A & B): Max. Inductance = 8 mH | Max. Capacitance = 0.3 μF
  • Non-Hydrogen Environments (Group C & D): Max. Inductance = 22 mH | Max. Capacitance = 7 μF

Installation and Maintenance

DIN Rail Mounting

Snap the module securely onto standard TS32 or TS35 DIN EN rails. The physical installation requires an absolute minimum rail length of 171 mm to guarantee stability and adequate side spacing inside the enclosure panel.

Field Connection Protocols

Connect field wires using copper conductors up to a maximum size of 2.5 mm² (AWG 14). Strip the wire insulation back exactly 7 mm (0.28 in). Secure the wire inside the terminal block by applying a precise tightening torque of 0.5 Nm (0.37 ft-lb) to avoid damage to the terminal frame.

Fuse Replacement Standards

If a group experiences a dead short circuit, verify loop integrity before replacing the fuse. Only use original manufacturer part numbers (SOC SHV12 250 mA) to maintain the certified non-incendive thermal thresholds. Note that the maximum sustained output current per fuse must not exceed 175 mA.

Engineering Advantages

Compact Footprint Optimization

Measuring just 170 mm in length, this module optimizes internal cabinet space compared to traditional terminal blocks combined with external fuse holders, providing high-density I/O allocation.

Reduced Total Cost of Ownership

By achieving Class I, Division 2 approval directly through internal current-limiting design, the assembly removes the requirement for expensive intrinsically safe galvanic isolators and dedicated grounding systems.

Global Safety Certifications

The module holds full industrial compliance stamps including CE, TÜV, UL, CSA, and FM, meeting the rigorous standards necessary for deployment in global refining, petrochemical, and chemical complexes.

Technical FAQs

Q1: Why is the maximum output current per fuse limited to 175 mA when the fuse itself is rated for 250 mA?
A1: The 175 mA limit enforces a safe engineering safety margin. This constraint prevents continuous operation near the thermal trip point of the fuse, preventing nuisance blowing caused by minor ambient temperature fluctuations or temporary current ripples.

Q2: What happens to the remaining 7 channels if one channel develops a short circuit to ground?
A2: If a short circuit draws current exceeding the fuse threshold on a single channel, the 250 mA common fuse for that specific group of 8 will open. This protects the system backplane but drops power to all 8 channels within that isolated group. The opposite group of 8 will continue running normally.

Q3: Can this module be used with non-certified standard digital input devices in hazardous areas?
A3: Yes, provided that the overall field circuit matches the non-incendive loop parameters (maximum loop resistance, inductance, and capacitance) defined for Gas Groups A-D. The current-limiting features of the FTA ensure that field wiring faults cannot generate a spark with sufficient thermal energy to ignite the atmosphere.

🏷️ Tags: Input Module
  • Arancione

Scalare (V/f)

Vettore

Alimentato a corrente alternata

  • Conferma il modello esatto, il numero di parte e le specifiche prima di ordinare.
  • Verifica la compatibilità con la tua macchina o i sistemi di controllo attuali.
  • Contatta sale@etowonauto.com o +8617859788089 per assistenza tecnica.
  • Esamina le opzioni di consegna, i tempi di attesa e i requisiti di spedizione.
  • Segui le istruzioni del produttore e le migliori pratiche durante l’installazione.

Gli articoli disponibili in magazzino vengono solitamente spediti lo stesso giorno lavorativo. Per i prodotti non attualmente disponibili, i tempi di spedizione possono variare in base alla disponibilità. La spedizione internazionale è disponibile e i costi di spedizione sono calcolati in base alla destinazione, al peso e al corriere scelto.

Le restituzioni sono accettate entro 30 giorni dal ricevimento, a condizione che gli articoli siano inutilizzati e nelle condizioni originali. Le spese di spedizione per la restituzione sono a carico del cliente. Si prega di contattarci prima di restituire qualsiasi articolo per ricevere l'autorizzazione al reso.

Per maggiori dettagli, si prega di consultare la nostra Politica di Spedizione e Reso.

Visualizza dettagli completi

GARANTISCI PRESTAZIONI AFFIDABILI DELLA MACCHINARIA

Trasforma la tua casa con le ultime soluzioni multi-elettroniche, dall'illuminazione intelligente ai dispositivi controllati tramite voce, tutti progettati per rendere la vita più facile, sicura e connessa. Ottimizza le tue operazioni con il Sistema di Monitoraggio Bently Nevada 3500, che offre il monitoraggio in tempo reale delle vibrazioni e delle condizioni delle macchine per prevenire guasti e massimizzare il tempo di attività.