SKU:MTL5061

MTL5061 Fire Smoke Detector Interface - MTL Instruments

Auf Lager (25 Einheiten), versandbereit
  • Manufacturer: MTL

  • Product No.: MTL5061

  • Product Type: Detector Interface

  • Product Origin: USA

  • Payment:T/T, Western Union

  • Weight: 110g

  • Shipping port: Xiamen

  • Warranty: 12 months

30-Tage-Rückgaberecht · 12 Monate Garantie
  • Schnelle Lieferung
  • Rund-um-die-Uhr Unterstützung
  • Qualitätssicherung

Beschreibung

MTL5061 Fire & Smoke Detector Interface

The MTL5061 from MTL Instruments is a loop-powered dual-channel interface designed for fire and smoke detectors in hazardous areas. This specialized unit provides reliable signal transmission from detectors to safe-area monitoring systems. 

Key Technical Specifications

  • Brand: MTL Instruments
  • Model: MTL5061
  • Product Type: Fire & Smoke Detector Interface
  • Channels: Two independent channels
  • Power Type: Loop-powered operation
  • Current Range: 1 to 40mA nominal
  • Response Time: 30ms maximum

Hazardous Area Certification

  • Detector Location: Zone 0, IIC, T4-T6 hazardous area
  • Division Rating: Division 1, Group A hazardous location
  • The MTL5061 maintains intrinsic safety for fire detection systems
  • It enables safe operation of detectors in explosive atmospheres

Electrical Performance

  • Current Range: 1 to 40mA nominal operating range
  • Transfer Accuracy: Better than 400µA at 20°C
  • Temperature Drift: <10µA/°C (-20 to 60°C)
  • Response Time: Settles within 30ms to 500µA of final value
  • Quiescent Current: <400µA per channel at 24V DC

Output Characteristics

  • Maximum Output Voltage: 28V from 300Ω
  • Minimum Output Voltage: Lower of Vin – (0.38 x mA) – 2V or 21V – (0.35 x mA)
  • Automatic voltage calculation based on current draw
  • Stable output performance across operating range

Power Requirements

  • Loop Supply Voltage: 6 to 35V DC operating range
  • Power Dissipation: 0.7W at 24V with 40mA signal per channel
  • Maximum Dissipation: 1.2W at 35V with 40mA signal per channel
  • Loop-powered design simplifies installation

Terminal Configuration

  • Channel 1 Output: Terminal 1 (Output –ve), Terminal 2 (Output +ve)
  • Channel 1 Input: Terminal 11 (Input –ve), Terminal 12 (Input +ve)
  • Channel 1 Earth: Terminal 3 for leakage detection
  • Channel 2 Output: Terminal 4 (Output –ve), Terminal 5 (Output +ve)
  • Channel 2 Input: Terminal 8 (Input –ve), Terminal 9 (Input +ve)
  • Channel 2 Earth: Terminal 6 for leakage detection

Safety Parameters

  • Safety Voltage: 28V maximum
  • Internal Resistance: 300Ω
  • Safety Current: 93mA maximum
  • Isolation Voltage: Um = 250V rms or DC
  • Comprehensive protection for fire safety applications

Frequently Asked Questions

  • What detectors is the MTL5061 designed for?
    It interfaces with conventional fire and smoke detectors in hazardous areas.
  • How does earth fault detection work?
    Optional 'non-fail' detection via MTL4220 unit allows continued operation during faults.
  • What is the response time for detector signals?
    It settles within 30ms to within 500µA of the final value.
  • Is reverse polarity protection included?
    Yes, the input circuit has integrated reverse polarity protection.
🏷️ Tags: Detector Interface

Skalar (V/f)

Vektor

Netzbetrieben

  • Bestätigen Sie vor der Bestellung das genaue Modell, die Teilenummer und die Spezifikationen.
  • Stellen Sie die Kompatibilität mit Ihrer aktuellen Maschine oder Steuerung sicher.
  • Kontaktieren Sie uns für technische Unterstützung unter sale@etowonauto.com oder +8617859788089.
  • Überprüfen Sie Lieferoptionen, Lieferzeiten und Versandanforderungen.
  • Folgen Sie bei der Installation den Herstelleranweisungen und bewährten Verfahren.

Vorrätige Artikel werden in der Regel noch am selben Werktag versandt. Bei Produkten, die derzeit nicht auf Lager sind, können die Versandzeiten je nach Verfügbarkeit variieren. Internationaler Versand ist möglich, und die Versandkosten werden basierend auf Zielort, Gewicht und gewähltem Versanddienstleister berechnet.

Rücksendungen werden innerhalb von 30 Tagen nach Erhalt akzeptiert, vorausgesetzt, die Artikel sind unbenutzt und im Originalzustand. Die Rücksendekosten trägt der Kunde. Bitte kontaktieren Sie uns vor der Rücksendung eines Artikels, um eine Rücksendegenehmigung zu erhalten.

Für weitere Details lesen Sie bitte unsere Versand- & Rückgaberichtlinie.

Vollständige Details anzeigen

SICHERN SIE ZUVERLÄSSIGE MASCHINENLEISTUNG

Verwandeln Sie Ihr Zuhause mit den neuesten Multi-Elektronik-Lösungen, von intelligenter Beleuchtung bis hin zu sprachgesteuerten Geräten – alle darauf ausgelegt, das Leben einfacher, sicherer und vernetzter zu machen. Optimieren Sie Ihre Abläufe mit dem Bently Nevada 3500 Überwachungssystem, das eine Echtzeit-Überwachung von Vibrationen und Maschinenzuständen bietet, um Ausfälle zu verhindern und die Betriebszeit zu maximieren.