Opis

MTL5061 Fire & Smoke Detector Interface

The MTL5061 from MTL Instruments is a loop-powered dual-channel interface designed for fire and smoke detectors in hazardous areas. This specialized unit provides reliable signal transmission from detectors to safe-area monitoring systems. 

Key Technical Specifications

  • Brand: MTL Instruments
  • Model: MTL5061
  • Product Type: Fire & Smoke Detector Interface
  • Channels: Two independent channels
  • Power Type: Loop-powered operation
  • Current Range: 1 to 40mA nominal
  • Response Time: 30ms maximum

Hazardous Area Certification

  • Detector Location: Zone 0, IIC, T4-T6 hazardous area
  • Division Rating: Division 1, Group A hazardous location
  • The MTL5061 maintains intrinsic safety for fire detection systems
  • It enables safe operation of detectors in explosive atmospheres

Electrical Performance

  • Current Range: 1 to 40mA nominal operating range
  • Transfer Accuracy: Better than 400µA at 20°C
  • Temperature Drift: <10µA/°C (-20 to 60°C)
  • Response Time: Settles within 30ms to 500µA of final value
  • Quiescent Current: <400µA per channel at 24V DC

Output Characteristics

  • Maximum Output Voltage: 28V from 300Ω
  • Minimum Output Voltage: Lower of Vin – (0.38 x mA) – 2V or 21V – (0.35 x mA)
  • Automatic voltage calculation based on current draw
  • Stable output performance across operating range

Power Requirements

  • Loop Supply Voltage: 6 to 35V DC operating range
  • Power Dissipation: 0.7W at 24V with 40mA signal per channel
  • Maximum Dissipation: 1.2W at 35V with 40mA signal per channel
  • Loop-powered design simplifies installation

Terminal Configuration

  • Channel 1 Output: Terminal 1 (Output –ve), Terminal 2 (Output +ve)
  • Channel 1 Input: Terminal 11 (Input –ve), Terminal 12 (Input +ve)
  • Channel 1 Earth: Terminal 3 for leakage detection
  • Channel 2 Output: Terminal 4 (Output –ve), Terminal 5 (Output +ve)
  • Channel 2 Input: Terminal 8 (Input –ve), Terminal 9 (Input +ve)
  • Channel 2 Earth: Terminal 6 for leakage detection

Safety Parameters

  • Safety Voltage: 28V maximum
  • Internal Resistance: 300Ω
  • Safety Current: 93mA maximum
  • Isolation Voltage: Um = 250V rms or DC
  • Comprehensive protection for fire safety applications

Frequently Asked Questions

  • What detectors is the MTL5061 designed for?
    It interfaces with conventional fire and smoke detectors in hazardous areas.
  • How does earth fault detection work?
    Optional 'non-fail' detection via MTL4220 unit allows continued operation during faults.
  • What is the response time for detector signals?
    It settles within 30ms to within 500µA of the final value.
  • Is reverse polarity protection included?
    Yes, the input circuit has integrated reverse polarity protection.
🏷️ Tags: Detector Interface

Skalar (V/f)

Wektor

Zasilany prądem zmiennym

  • Potwierdź dokładny model, numer części oraz specyfikacje przed złożeniem zamówienia.
  • Upewnij się, że jest kompatybilny z Twoimi obecnymi maszynami lub systemami sterowania.
  • Skontaktuj się pod adresem sale@etowonauto.com lub pod numerem +8617859788089, aby uzyskać pomoc techniczną.
  • Sprawdź opcje dostawy, czas realizacji oraz wymagania dotyczące wysyłki.
  • Postępuj zgodnie z instrukcjami producenta i najlepszymi praktykami podczas instalacji.

Produkty dostępne w magazynie są zazwyczaj wysyłane tego samego dnia roboczego. W przypadku produktów chwilowo niedostępnych czas wysyłki może się różnić w zależności od dostępności. Oferujemy wysyłkę międzynarodową, a koszty przesyłki są obliczane na podstawie miejsca docelowego, wagi oraz wybranego przewoźnika.

Zwroty są akceptowane w ciągu 30 dni od otrzymania, pod warunkiem, że produkty są nieużywane i w oryginalnym stanie. Koszty zwrotu ponosi klient. Prosimy o kontakt przed zwrotem jakiegokolwiek produktu, aby uzyskać autoryzację zwrotu.

Więcej informacji znajdziesz w naszej Polityce wysyłki i zwrotów.

Pokaż kompletne dane

ZAPEWNIJ NIEZAWODNĄ PRACĘ MASZYN

Przekształć swój dom dzięki najnowszym rozwiązaniom multi-elektronicznym, od inteligentnego oświetlenia po urządzenia sterowane głosem — wszystko zaprojektowane, aby życie było łatwiejsze, bezpieczniejsze i bardziej połączone.

Optymalizuj swoje operacje dzięki systemowi monitorowania Bently Nevada 3500, oferującemu monitorowanie drgań i stanu maszyn w czasie rzeczywistym, aby zapobiegać awariom i maksymalizować czas pracy.