{"product_id":"honeywell-10302-1-1-watchdog-repeater-power-monitor-module","title":"Honeywell 10302\/1\/1 Watchdog Repeater Power Monitor Module","description":"\u003ch2\u003eProduct Overview\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong style=\"color: #0066cc;\"\u003e10302\/1\/1 Watchdog Repeater\u003c\/strong\u003e monitors 5 Vdc and 24 Vdc power to I\/O modules. It delivers a watchdog output to output modules, ensuring system integrity in multi-PSU or redundant I\/O configurations.\u003c\/p\u003e\n\n\u003ch2\u003eTechnical Configuration\u003c\/h2\u003e\n\u003cp\u003eInstalls via horizontal bus in I\/O racks (positions 1 to 18). Must be placed in the I\/O section it monitors. Hot swappable, but exchange may trigger a Central Part shutdown. Occupies 4 TE, 3 HE (4 HP, 3U).\u003c\/p\u003e\n\n\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\n\u003ctable\u003e\n    \u003ctr\u003e\n\u003ctd\u003eType Number\u003c\/td\u003e\n\u003ctd\u003e10302\/1\/1\u003c\/td\u003e\n\u003c\/tr\u003e\n    \u003ctr\u003e\n\u003ctd\u003eApprovals\u003c\/td\u003e\n\u003ctd\u003eCE, TUV, UL\u003c\/td\u003e\n\u003c\/tr\u003e\n    \u003ctr\u003e\n\u003ctd\u003eSpace Requirements\u003c\/td\u003e\n\u003ctd\u003e4 TE, 3 HE (4 HP, 3U)\u003c\/td\u003e\n\u003c\/tr\u003e\n    \u003ctr\u003e\n\u003ctd\u003e5 Vdc Supply Current\u003c\/td\u003e\n\u003ctd\u003e35 mA (without WDROUT)\u003c\/td\u003e\n\u003c\/tr\u003e\n    \u003ctr\u003e\n\u003ctd\u003e24 Vdc Supply Current\u003c\/td\u003e\n\u003ctd\u003e25 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n    \u003ctr\u003e\n\u003ctd\u003eWDG1 + WDG2 Input Current\u003c\/td\u003e\n\u003ctd\u003e0.1 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n    \u003ctr\u003e\n\u003ctd\u003eWDR OUT Max Output Current\u003c\/td\u003e\n\u003ctd\u003e900 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n    \u003ctr\u003e\n\u003ctd\u003eKey Coding (Module)\u003c\/td\u003e\n\u003ctd\u003eHoles A27; Pins C11, C23, C27\u003c\/td\u003e\n\u003c\/tr\u003e\n    \u003ctr\u003e\n\u003ctd\u003eKey Coding (Rack)\u003c\/td\u003e\n\u003ctd\u003eBlind Spots C3, C19, C31; Large Pins A27\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/table\u003e\n\n\u003ch2\u003eInstallation Guide\u003c\/h2\u003e\n\u003cp\u003eInstall the \u003cstrong style=\"color: #0066cc;\"\u003e10302\/1\/1\u003c\/strong\u003e in any I\/O rack slot (1 to 18). Ensure firm horizontal bus connection. Place it in the I\/O section it supervises. Verify key coding matches backplane. Plan maintenance windows if shutdown is a concern.\u003c\/p\u003e\n\n\u003ch2\u003eEngineering Advantages\u003c\/h2\u003e\n\u003cp\u003eLow power draw (35 mA at 5V, 25 mA at 24V) reduces heat. 900 mA WDR OUT capacity supports multiple devices. CE, TUV, UL approvals confirm reliability. Seamlessly integrates with Honeywell TSI and control systems.\u003c\/p\u003e\n\n\u003ch2\u003eFrequently Asked Questions\u003c\/h2\u003e\n\u003cp\u003e\u003cstrong\u003eQ1:\u003c\/strong\u003e What happens if the monitored 5 Vdc or 24 Vdc supply fails?\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eA1:\u003c\/strong\u003e WDR OUT de energizes, sending output modules to a safe state.\u003c\/p\u003e\n\n\u003cp\u003e\u003cstrong\u003eQ2:\u003c\/strong\u003e Can it work in redundant power supply setups?\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eA2:\u003c\/strong\u003e Yes, it is designed for multi-PSU and mixed redundant I\/O configurations.\u003c\/p\u003e\n\n\u003cp\u003e\u003cstrong\u003eQ3:\u003c\/strong\u003e Is it compatible with older Honeywell I\/O racks?\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eA3:\u003c\/strong\u003e Yes, with standard racks that support horizontal bus and matching key coding.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":52687534456964,"sku":"10302\/1\/1","price":215.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0958\/7454\/7844\/files\/10302.jpg?v=1787402777","url":"https:\/\/www.etowonauto.com\/uz\/products\/honeywell-10302-1-1-watchdog-repeater-power-monitor-module","provider":"Etowon Auto","version":"1.0","type":"link"}