{"product_id":"ac-voltage-input-module-ic694mdl250-ge-fanuc","title":"AC Voltage Input Module IC694MDL250 GE Fanuc","description":"\u003ch2\u003eGE Fanuc IC694MDL250 16-Point Isolated Input Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eGE Fanuc IC694MDL250\u003c\/strong\u003e is a 16-point discrete input module for PACSystem RX3i. Formerly by GE Intelligent Platforms, now Emerson Automation, it features individually isolated channels rated at 120 Volts AC. This high-voltage module supports hot-swap and delivers reliable performance for industrial applications.\u003c\/p\u003e\n\u003ch2\u003eTechnical Specifications\u003c\/h2\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eBrand:\u003c\/strong\u003e GE Fanuc\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eModel:\u003c\/strong\u003e \u003cstrong\u003eIC694MDL250\u003c\/strong\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eSeries:\u003c\/strong\u003e PACSystem RX3i\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Points:\u003c\/strong\u003e 16 individually isolated channels\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eNominal Voltage:\u003c\/strong\u003e 120 Volts AC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Voltage Range:\u003c\/strong\u003e 0-132 VAC (47-63 Hz)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOn-State Voltage:\u003c\/strong\u003e 70-132 VAC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOff-State Voltage:\u003c\/strong\u003e 0-20 VAC\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Current:\u003c\/strong\u003e 14.5 mA typical, 7 mA per channel\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOn-State Current:\u003c\/strong\u003e 6 mA\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eOff-State Current:\u003c\/strong\u003e 2.5 mA\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eResponse Time:\u003c\/strong\u003e 30 ms on, 45 ms off maximum\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCurrent Draw:\u003c\/strong\u003e 60 mA from 5 VDC backplane bus\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eInput Filter Times:\u003c\/strong\u003e 20-2540 ms in 20 ms increments (CPU configurable)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eIsolation:\u003c\/strong\u003e 250V continuous optical, 1500V AC for 1 minute\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCommunication:\u003c\/strong\u003e RS-485, high-speed serial bus\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMounting:\u003c\/strong\u003e Panel or DIN Rail\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConnectors:\u003c\/strong\u003e IC694TBBx32 or IC694TBSx32 terminal blocks\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCertifications:\u003c\/strong\u003e UL 508, CSA C22.2 No 142M1987, Class 1 Division 2 Groups A,B,C,D\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eCPU Requirement:\u003c\/strong\u003e Firmware version 3.5 or later\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProduct Lifecycle:\u003c\/strong\u003e Active\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch2\u003eInstallation\u003c\/h2\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eSlot compatibility:\u003c\/strong\u003e Fits any available slot in PACSystem RX3i racks\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eConfiguration options:\u003c\/strong\u003e Use as local I\/O in CPU rack or distributed I\/O node with communication adapters\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMounting:\u003c\/strong\u003e Panel or DIN rail mounting base\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eEnvironment:\u003c\/strong\u003e Class 1 Division 2 rated, clean environment with minimal EMC noise recommended\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eTerminal blocks:\u003c\/strong\u003e Requires IC694TBBx32 or IC694TBSx32 connectors (sold separately)\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eProgramming connection:\u003c\/strong\u003e RS-485 port connects to programming terminal or PC\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch2\u003ePackage Includes\u003c\/h2\u003e\n\u003cul\u003e\n\u003cli\u003e1 x \u003cstrong\u003eIC694MDL250\u003c\/strong\u003e discrete input module\u003c\/li\u003e\n\u003cli\u003eTerminal blocks sold separately\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch2\u003eShipping\u003c\/h2\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eCarriers:\u003c\/strong\u003e FedEx, UPS, DHL\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch2\u003eFAQ\u003c\/h2\u003e\n\u003cul\u003e\n\u003cli\u003e\u003cstrong\u003eWhat CPU firmware does the IC694MDL250 require?\u003c\/strong\u003e\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eThe \u003cstrong\u003eIC694MDL250\u003c\/strong\u003e requires CPU firmware version 3.5 or later for normal operation.\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\u003cstrong\u003eCan this module continue working if one channel fails?\u003c\/strong\u003e\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eYes, individual channel isolation allows the \u003cstrong\u003eIC694MDL250\u003c\/strong\u003e to operate normally even with a failed input channel.\u003c\/p\u003e\n\u003cul\u003e\n\u003cli\u003e\u003cstrong\u003eWhat terminal blocks work with this module?\u003c\/strong\u003e\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003eUse IC694TBBx32 or IC694TBSx32 connectors. These terminal blocks are sold separately.\u003c\/p\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":51047938359428,"sku":"IC694MDL250","price":205.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0958\/7454\/7844\/files\/IC694MDL250-1.jpg?v=1772288396","url":"https:\/\/www.etowonauto.com\/tr\/products\/ac-voltage-input-module-ic694mdl250-ge-fanuc","provider":"Etowon Auto","version":"1.0","type":"link"}