{"product_id":"is200tdbth6a-ge-terminal-board-mark-vie-24-input-12-relay","title":"IS200TDBTH6A GE Terminal Board Mark VIe 24 Input 12 Relay","description":"\u003ch2\u003eGE IS200TDBTH6A Discrete I\/O Terminal Board\u003c\/h2\u003e\n\n\u003ch3\u003eProduct Overview\u003c\/h3\u003e\n\u003cp\u003eThe \u003cstrong style=\"color: #1a5f7a;\"\u003eGE IS200TDBTH6A\u003c\/strong\u003e is a Discrete Input\/Output Terminal Board from the Mark VIe Series, designed for Distributed Control Systems. It features 24 group isolated contact inputs and 12 form-C relay outputs. The board supports nominal 24, 48, or 125 Vdc wetting voltage and accepts an option card for expanded relay functionality. Weight is 1.2 kg.\u003c\/p\u003e\n\n\u003ch3\u003eSpecifications\u003c\/h3\u003e\n\u003ctable style=\"width: 100%; border-collapse: collapse; background: #f4f7fa; border: 1px solid #b8c9d6;\"\u003e\n\u003cthead\u003e\n\u003ctr style=\"background: #b8c9d6; color: #1a2a3a;\"\u003e\n\u003cth style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eParameter\u003c\/th\u003e\n\u003cth style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eValue\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eBrand\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eGeneral Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eModel\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eIS200TDBTH6A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eSeries\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eMark VIe \/ Mark VI Speedtronic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eFunctional Acronym\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eTDBT\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eProduct Type\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eDiscrete I\/O Terminal Board\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eInput Channels\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003e24 group isolated contact inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eRelay Outputs\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003e12 form-C relay outputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eWetting Voltage\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003e24, 48, or 125 Vdc nominal\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eInput Current (Ch 1-21)\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003e2.5 mA (resistance limited)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eInput Current (Ch 22-24)\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003e10 mA (resistance limited)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eAC Voltage Rejection\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003e12 V RMS\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003ePower Requirement\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003e+5 Vdc\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eInput Filter\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eHardware filter\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eOperating Temperature\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003e-30 °C to +65 °C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eMounting Type\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eDIN Rail or Flat Mount\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eDimensions (W x H)\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003e178 x 330 mm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eWeight\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003e1.2 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eManual\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eGEH-6721L\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eCountry of Origin\u003c\/td\u003e\n\u003ctd style=\"padding: 6px; border: 1px solid #8ba3b0;\"\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul style=\"list-style-type: none; padding-left: 0;\"\u003e\n\u003cli\u003e24 group isolated contact inputs with noise suppression\u003c\/li\u003e\n\u003cli\u003e12 form-C relay outputs for flexible control\u003c\/li\u003e\n\u003cli\u003eSupports 24, 48, or 125 Vdc wetting voltage\u003c\/li\u003e\n\u003cli\u003eAccepts optional relay option board for expanded functionality\u003c\/li\u003e\n\u003cli\u003eNo hardware configurations or jumpers on TDBT\u003c\/li\u003e\n\u003cli\u003eDIN rail or flat panel mounting options\u003c\/li\u003e\n\u003cli\u003eCompatible with PDIO I\/O packs and Mark VIe systems\u003c\/li\u003e\n\u003cli\u003eThree PDIO connection points (JR1, JS1, JT1)\u003c\/li\u003e\n\u003cli\u003eResettable polymer PTC fuses for 24 Vdc supply\u003c\/li\u003e\n\u003cli\u003eConformal coating for environmental protection\u003c\/li\u003e\n\u003cli\u003eMade in USA (Salem, Virginia)\u003c\/li\u003e\n\u003c\/ul\u003e\n\n\u003ch3\u003eInstallation Notes\u003c\/h3\u003e\n\u003cp\u003eMount the TDBT on a DIN rail using the sheet metal carrier with plastic insulator. Connect field wiring using #18 AWG wires to the terminal blocks. Lower terminals (TB2) connect input contact circuits; upper terminals (TB1) connect relay outputs. Use separate bracket for end shields. For relay option boards, plug into JW1 and JW2 connectors.\u003c\/p\u003e\n\n\u003ch3\u003eRelay Output Configuration\u003c\/h3\u003e\n\u003cp\u003eThe TDBT provides 12 form-C relay outputs. When using the option board, connect to JW1 and JW2. Six jumpers on the WROBH1 option board enable or disable each relay. Remove jumpers when dry contacts are used and power distribution is not required. All jumpers are assembled by default during production.\u003c\/p\u003e\n\n\u003ch3\u003eFAQs\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong style=\"color: #1a5f7a;\"\u003eQ1:\u003c\/strong\u003e What is the input wetting voltage range?\u003c\/p\u003e\n\u003cp\u003e\u003cstrong style=\"color: #1a5f7a;\"\u003eA1:\u003c\/strong\u003e 16-32 Vdc for 24V, 32-64 Vdc for 48V, and 100-145 Vdc for 125V nominal settings.\u003c\/p\u003e\n\n\u003cp\u003e\u003cstrong style=\"color: #1a5f7a;\"\u003eQ2:\u003c\/strong\u003e Is this board compatible with the Mark VIe system?\u003c\/p\u003e\n\u003cp\u003e\u003cstrong style=\"color: #1a5f7a;\"\u003eA2:\u003c\/strong\u003e Yes. The TDBT works with PDIO I\/O packs via D-type connectors communicating with controllers over Ethernet.\u003c\/p\u003e\n\n\u003cp\u003e\u003cstrong style=\"color: #1a5f7a;\"\u003eQ3:\u003c\/strong\u003e Does the board require any hardware configuration?\u003c\/p\u003e\n\u003cp\u003e\u003cstrong style=\"color: #1a5f7a;\"\u003eA3:\u003c\/strong\u003e No. The TDBT has no hardware configurations or jumpers. Configuration is done via software.\u003c\/p\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":52646026346628,"sku":"IS200TDBTH6A","price":176.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0958\/7454\/7844\/files\/IS200TDBTH6A-2_258f241c-c98b-4cee-9651-7a0b44f4679c.jpg?v=1786786337","url":"https:\/\/www.etowonauto.com\/pl\/products\/is200tdbth6a-ge-terminal-board-mark-vie-24-input-12-relay","provider":"Etowon Auto","version":"1.0","type":"link"}